Worked example
Example: 400 kvar on 25 MVA bus. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Short-circuit level at the bus | 25.000 MVA |
| Capacitor bank | 400.00 kvar |
| System frequency | 50.000 Hz |
| Transformer rating (for the check) | 1,600.0 kVA |
| Transformer impedance | 6.0000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Resonant harmonic order | 7.9057 |
| Resonant frequency | 395.28 Hz |
| Order using transformer impedance only | 8.1650 |
Open this example in the calculator and change any input.
Formula
\(h_r = \sqrt{\frac{S_{sc}}{Q_C}}, \quad f_r = h_rf, \quad h_{r,T} = \sqrt{\frac{S_T}{z_TQ_C}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(S_{sc}\) | Short-circuit level at the bus | VA |
| \(Q_C\) | Capacitor bank | var |
| \(f\) | System frequency | 1/s |
| \(S_T\) | Transformer rating (for the check) | VA |
| \(z_T\) | Transformer impedance | - |
| \(h_r\) | Resonant harmonic order | - |
| \(f_r\) | Resonant frequency | 1/s |
| \(h_{r,T}\) | Order using transformer impedance only | - |
Method and standards
Parallel resonance.
Where it is used
- Capacitor bank sizing checks.
- Explaining capacitor failures.
Common mistakes
- Ignoring stages of an automatic bank (each step moves resonance).
- Using upstream fault level that ignores the transformer.
Assumptions and limits
- Inductive supply; resistance neglected.
- Resonance within ±0.5 of the 3rd, 5th, 7th, 11th or 13th harmonic is flagged (a screening rule of thumb); for a stepped bank check each step.
References
- Parallel resonance h_r = √(S_sc/Q_C) (IEEE 519 application practice)
Questions and answers
Why does a capacitor resonate with the supply?
The supply looks inductive from the bus; at h = √(S_sc/Q_C) the capacitor's reactance equals it and impedance peaks.
Why is the 5th the danger?
Six-pulse drives produce strong 5th and 7th harmonics; a resonance near them amplifies voltage distortion and overloads capacitors.
What do the defaults represent?
400 kvar on a bus with a 25 MVA short-circuit level, fed by a 1.6 MVA, 6 % transformer.