Worked example
Example: 9.5 N/m, 250 m span, 15 kN. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Weight of the conductor per unit length | 9.5000 N/m |
| Span between supports | 250.00 m |
| Horizontal tension | 15.000 kN |
Applying the formula below gives:
| Result | Value |
|---|---|
| Sag by the parabola w L² / (8 T) | 4.9479 m |
| Sag by the catenary | 4.9505 m |
| Conductor length in the span | 250.26 m |
| Tension at the supports T + w S_c | 15.047 kN |
Open this example in the calculator and change any input.
Formula
\(S = \frac{w L^2}{8 T}, \quad S_c = \frac{T}{w}\left(\cosh\frac{w L}{2 T} - 1\right), \quad l_c = \frac{2T}{w}\sinh\frac{wL}{2T}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(w\) | Weight of the conductor per unit length | N/m |
| \(L\) | Span between supports | m |
| \(T\) | Horizontal tension | N |
| \(S\) | Sag by the parabola w L² / (8 T) | m |
| \(S_c\) | Sag by the catenary | m |
| \(l_c\) | Conductor length in the span | m |
| \(T_{max}\) | Tension at the supports T + w S_c | N |
Method and standards
Statics of a hanging conductor.
Where it is used
- Distribution line stringing.
- Clearance checks.
- Electrical examinations.
Common mistakes
- Using mass (kg/m) as weight.
- Ignoring ice and wind.
Assumptions and limits
- Supports at the same level.
- A sag over a tenth of the span is flagged (the parabola is then inadequate); wL/(2T) above 5 is rejected as an unrealistically slack conductor.
References
- Parabolic approximation and catenary of a uniform flexible conductor (textbook)
Questions and answers
What is the sag of a 250 m span, 9.5 N/m conductor at 15 kN?
4.95 m.
When is the parabola good enough?
When the sag is under about a tenth of the span.
How does temperature matter?
The conductor lengthens when hot, so sag rises and tension falls.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.