Worked example
Example: 25 mm copper at 50 Hz. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Frequency | 50.000 Hz |
| Conductor diameter | 25.000 mm |
| Resistivity | 1.7240e-08 Ω·m |
| Relative permeability | 1.0000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Skin depth | 9.3455 mm |
| Diameter-to-skin-depth ratio | 2.6751 |
| AC-to-DC resistance ratio | 1.0633 |
Open this example in the calculator and change any input.
Formula
\(\delta = \sqrt{\frac{\rho}{\pi f\mu_0\mu_r}}, \quad \frac{R_{ac}}{R_{dc}} = \mathrm{Re}\left[\frac{kr}{2}\frac{J_0(kr)}{J_1(kr)}\right],\ k = \frac{1 - j}{\delta}; \quad \approx \frac x4 + \frac14 + \frac{3}{16x}\ (x = d/\delta > 20)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(f\) | Frequency | 1/s |
| \(d\) | Conductor diameter | m |
| \(\rho\) | Resistivity | Ω·m |
| \(\mu_r\) | Relative permeability | - |
| \(\delta\) | Skin depth | m |
| \(d/\delta\) | Diameter-to-skin-depth ratio | - |
| \(R_{ac}/R_{dc}\) | AC-to-DC resistance ratio | - |
| \(\mu_0\) | Magnetic constant, 1.256 637 062 12 × 10⁻⁶ | H/m |
| \(k\) | Complex propagation constant (1 − j)/δ | 1/m |
| \(r\) | Conductor radius d/2 | m |
| \(J_0, J_1\) | Bessel functions of the first kind | - |
| \(x\) | d/δ | - |
Method and standards
Exact Bessel solution (power series), asymptotic form for very large d/δ.
Where it is used
- Busbar and large cable design.
- High-frequency induction heating.
Common mistakes
- Ignoring proximity effect in bundles.
- Using copper resistivity at 20 °C for hot conductors.
Assumptions and limits
- Isolated round conductor.
- Above d/δ = 20 the three-term asymptotic form r/(2δ) + 1/4 + 3δ/(32r) (with r = d/2) is used; it agrees with the series solution to about 0.002 % at the switch, and closer above it.
References
- Skin depth δ = √(ρ/(πfμ)); exact Bessel-function solution for a round wire
- Z/R_dc = (kr/2)J₀(kr)/J₁(kr) with k = (1 − j)/δ (Ramo, Whinnery and Van Duzer, Fields and Waves in Communication Electronics, 3rd ed. (Wiley, 1994))
Questions and answers
What is skin depth?
The depth at which current density falls to 37 % of its surface value; current crowds into a layer about this thick.
When does it matter at 50 Hz?
For copper conductors above about 20 mm diameter and for steel (high μ), where δ is only about 1 mm.
What do the defaults represent?
A 25 mm copper conductor at 50 Hz.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.