Worked example
Example: 95 mm² copper XLPE, 90 to 250 °C, 1 s; 20 kA. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Conductor | Copper |
| Conductor cross-section | 95.000 mm² |
| Duration of the fault | 1.0000 s |
| Conductor temperature before the fault | 90.000 °C |
| Highest temperature allowed at the end of the fault | 250.00 °C |
| Fault current, RMS symmetrical (to find the size needed) | 20.000 kA |
Applying the formula below gives:
| Result | Value |
|---|---|
| Factor k (A·s^½/mm²) | 142.87 |
| Current the conductor withstands for the time | 13.573 kA |
| Smallest cross-section for the fault current | 139.98 mm² |
Open this example in the calculator and change any input.
Formula
\(k = \sqrt{\frac{Q_c (\beta + 20)}{\rho_{20}} \ln\frac{\beta + \theta_f}{\beta + \theta_i}}, \quad I_{max} = \frac{k\, S}{\sqrt t}, \quad S_{min} = \frac{I_k \sqrt t}{k}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\text{metal}\) | Conductor | - |
| \(S\) | Conductor cross-section | m² |
| \(t\) | Duration of the fault | s |
| \(\theta_i\) | Conductor temperature before the fault | K |
| \(\theta_f\) | Highest temperature allowed at the end of the fault | K |
| \(I_k\) | Fault current, RMS symmetrical (to find the size needed) | A |
| \(k\) | Factor k (A·s^½/mm²) | - |
| \(I_{max}\) | Current the conductor withstands for the time | A |
| \(S_{min}\) | Smallest cross-section for the fault current | m² |
Method and standards
All the fault energy heats the conductor; resistance rises with temperature.
Where it is used
- Checking cable size against the protection clearing time.
- Earth and protective conductors.
Common mistakes
- Using the breaker rating instead of the clearing time.
- Wrong starting temperature.
Assumptions and limits
- Adiabatic; conductor only.
- I_k is the RMS symmetrical current; the DC component is neglected. For faults shorter than about 0.1 s the asymmetry matters: use the protective device's let-through I²t instead.
References
- IEC 60949:1988 (adiabatic short-circuit calculation; material constants of Table I)
Questions and answers
What can 95 mm² copper carry for 1 s from 90 °C to 250 °C?
k = 143, so about 13.6 kA.
What size for 20 kA for 1 s?
140 mm² at least: choose the next standard size.
Where do the temperatures come from?
The insulation's operating and short-circuit limits in the cable standard or maker's data.