DC Cable Voltage Drop and Size (Solar, Battery)

Voltage drop and power loss of a two-wire DC cable for solar strings, batteries and DC systems, and the conductor size needed for an allowed drop.

Thermal power plantProcess steam and utilitiesIEC 60364 (low-voltage installations)

Inputs

Examples: 48 V, 50 A, 15 m, 16 mm², 2 %PV string 800 V, 11 A, 120 m, 4 mm², 1.5 %12 V, 30 A, 5 m, 10 mm² aluminium, 3 %

Default: copper in service (1.25 × the 20 °C value, IEC 60364-5-52 Annex G). Aluminium 0.036 Ω·mm²/m.

Results

The drop with this cross-section exceeds the allowed value: use at least A_min.

Voltage drop 2 ρ L I / A2.1094V
Voltage drop as a share of the system voltage4.3945%
Power lost in the cable105.47W
Smallest cross-section for the allowed drop35.156mm²

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 48 V, 50 A, 15 m, 16 mm², 2 %. The inputs, in the units selected above:

InputValue
System voltage48.000 V
Current50.000 A
One-way cable length15.000 m
Conductor cross-section16.000 mm²
Resistivity of the conductor in service0.022500 Ω·mm²/m
Allowed voltage drop2.0000 %

Applying the formula below gives:

ResultValue
Voltage drop 2 ρ L I / A2.1094 V
Voltage drop as a share of the system voltage4.3945 %
Power lost in the cable105.47 W
Smallest cross-section for the allowed drop35.156 mm²

Open this example in the calculator and change any input.

Formula

\(\Delta V = \frac{2 \rho L I}{A}, \quad A_{min} = \frac{2 \rho L I}{u_{max} V}\)

Variables

Symbol Meaning SI unit
\(V\) System voltage V
\(I\) Current A
\(L\) One-way cable length m
\(A\) Conductor cross-section m²
\(\rho\) Resistivity of the conductor in service Ω·m
\(u_{max}\) Allowed voltage drop -
\(\Delta V\) Voltage drop 2 ρ L I / A V
\(u\) Voltage drop as a share of the system voltage -
\(P_{loss}\) Power lost in the cable W
\(A_{min}\) Smallest cross-section for the allowed drop m²

Method and standards

Resistance of the go and return conductors.

Where it is used

  • Solar string and battery cables.
  • DC control supplies.

Common mistakes

  • Using one-way resistance.
  • Sizing on drop and not checking current rating.

Assumptions and limits

  • Resistive drop only.
  • A drop above the allowed u_max is flagged.

References

  • ΔV = 2 ρ L I / A (go and return)
  • IEC 60364-5-52 Annex G (conductor resistivity in service)

Questions and answers

What drop does 50 A cause over 15 m of 16 mm² at 48 V?

2.11 V, 4.4 %.

What size keeps it to 2 %?

35 mm² at least.

Why are low-voltage DC cables so thick?

The same power at lower voltage needs more current, and the allowed drop in volts is smaller.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.