Worked example
Example: 550 W module, 5 °C to 70 °C, 1 100 V inverter. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Module open-circuit voltage at STC | 49.500 V |
| Module maximum-power voltage at STC | 41.500 V |
| Temperature coefficient of Voc, per °C | -0.27000 % |
| Temperature coefficient of Vmp (or Pmax), per °C | -0.35000 % |
| Coldest cell temperature (lowest site ambient at sunrise) | 5.0000 °C |
| Hottest cell temperature in operation | 70.000 °C |
| Inverter maximum DC input voltage | 1,100.0 V |
| Inverter lowest MPPT voltage | 200.00 V |
| Inverter highest MPPT voltage | 1,000.0 V |
Applying the formula below gives:
| Result | Value |
|---|---|
| Module Voc at the coldest temperature | 52.173 V |
| Module Vmp at the hottest temperature | 34.964 V |
| Module Vmp at the coldest temperature | 44.405 V |
| Most modules per string (inverter maximum voltage) | 21.000 |
| Most modules per string to stay inside the MPPT range | 22.000 |
| Fewest modules per string (MPPT lowest voltage when hot) | 6.0000 |
Open this example in the calculator and change any input.
Formula
\(V_{oc,cold} = V_{oc} \left[1 + \beta_{oc} (T_{min} - 25\,°\text{C})\right]\)
\(V_{mp,hot} = V_{mp} \left[1 + \beta_{mp} (T_{max} - 25\,°\text{C})\right]\)
\(N_{max} = \left\lfloor \frac{V_{max}}{V_{oc,cold}} \right\rfloor, \quad N_{MPP,max} = \left\lfloor \frac{V_{MPP,max}}{V_{mp,cold}} \right\rfloor, \quad N_{min} = \left\lceil \frac{V_{MPP,min}}{V_{mp,hot}} \right\rceil\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V_{oc}\) | Module open-circuit voltage at STC | V |
| \(V_{mp}\) | Module maximum-power voltage at STC | V |
| \(\beta_{oc}\) | Temperature coefficient of Voc, per °C | - |
| \(\beta_{mp}\) | Temperature coefficient of Vmp (or Pmax), per °C | - |
| \(T_{min}\) | Coldest cell temperature (lowest site ambient at sunrise) | K |
| \(T_{max}\) | Hottest cell temperature in operation | K |
| \(V_{max}\) | Inverter maximum DC input voltage | V |
| \(V_{MPP,min}\) | Inverter lowest MPPT voltage | V |
| \(V_{MPP,max}\) | Inverter highest MPPT voltage | V |
| \(V_{oc,cold}\) | Module Voc at the coldest temperature | V |
| \(V_{mp,hot}\) | Module Vmp at the hottest temperature | V |
| \(V_{mp,cold}\) | Module Vmp at the coldest temperature | V |
| \(N_{max}\) | Most modules per string (inverter maximum voltage) | - |
| \(N_{MPP,max}\) | Most modules per string to stay inside the MPPT range | - |
| \(N_{min}\) | Fewest modules per string (MPPT lowest voltage when hot) | - |
Method and standards
Module voltages are corrected linearly from standard test conditions (25 °C cell) with the data-sheet coefficients. The string must stay below the inverter maximum at the coldest Voc, and inside the MPPT window at the hottest and coldest Vmp.
Where it is used
- Designing rooftop and ground-mount PV strings.
- Checking an inverter choice for a module.
- Checking strings after a module change.
Common mistakes
- Using the Pmax coefficient for Voc.
- Using average ambient instead of record low.
- Forgetting the string current must suit the inverter input too.
Assumptions and limits
- Linear temperature coefficients; irradiance effects on Voc not included.
- Cell temperature at the hottest case estimated by you.
- Use the Vmp coefficient where the data sheet gives it. The Pmax coefficient is usually larger in magnitude: it makes N_min conservative but N_MPP,max less so.
- The page warns when even one module exceeds the inverter maximum, and when the inverter maximum is below its MPPT high voltage.
References
- IEC 61215 / IEC 60904-3 standard test conditions
- Module temperature coefficients from the data sheet
Questions and answers
How many 49.5 V modules fit a 1 100 V inverter?
At 5 °C the module Voc rises to 52.2 V, so 21 modules give 1 096 V. More would exceed the inverter maximum on a cold morning.
What sets the fewest?
The hot Vmp: at 70 °C the module Vmp falls to 35.0 V, so a 200 V MPPT minimum needs at least 6 modules.
Which temperature should I use for the coldest case?
The lowest site ambient at sunrise, when the modules are cold but already lit; cell temperature then equals ambient.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.