Worked example
Example: 5 kWh/day, 48 V, 4.5 h, 2 days. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Daily energy use (Wh) | 5,000.0 - |
| Peak sun hours (design month) | 4.5000 - |
| System efficiency (wiring, controller, inverter) | 75.000 % |
| Battery system voltage | 48.000 V |
| Days of autonomy | 2.0000 - |
| Usable depth of discharge | 50.000 % |
| Module short-circuit current | 13.500 A |
| Module rating | 540.00 W |
Applying the formula below gives:
| Result | Value |
|---|---|
| PV array power | 1.4815 kW |
| Modules (rounded up) | 3.0000 |
| Battery capacity at system voltage (Ah) | 555.56 |
| Charge controller output current (MPPT: 1.25 × array power / battery voltage) | 42.188 A |
Open this example in the calculator and change any input.
Formula
\(P_{PV} = \frac{E_d}{PSH\cdot\eta_s}, \quad C = \frac{E_dn}{V_{sys}DoD\,\eta_s}, \quad I_{cc} = \frac{1.25\,n_{mod}P_{mod}}{V_{sys}}\ (\text{MPPT}), \quad I_{PWM} = 1.25\,n_p I_{sc,mod}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(E_d\) | Daily energy use (Wh) | - |
| \(PSH\) | Peak sun hours (design month) | - |
| \(\eta_s\) | System efficiency (wiring, controller, inverter) | - |
| \(V_{sys}\) | Battery system voltage | V |
| \(n\) | Days of autonomy | - |
| \(DoD\) | Usable depth of discharge | - |
| \(I_{sc,mod}\) | Module short-circuit current | A |
| \(P_{mod}\) | Module rating | W |
| \(P_{PV}\) | PV array power | W |
| \(n_{mod}\) | Modules (rounded up) | - |
| \(C\) | Battery capacity at system voltage (Ah) | - |
| \(I_{cc}\) | Charge controller output current (MPPT: 1.25 × array power / battery voltage) | A |
| \(I_{PWM}\), \(n_p\) | PWM controller current (given in a note) and number of parallel strings | A, - |
Method and standards
Energy balance.
Where it is used
- Remote instrumentation and telemetry.
- Off-grid buildings and pumps.
Common mistakes
- Using annual average sun hours.
- Ignoring battery efficiency.
Assumptions and limits
- Daily balance in the design month.
- The battery capacity divides by the whole system efficiency, which also includes PV-side losses not in the discharge path: slightly conservative. Module temperature derating is not included.
- The output current is for an MPPT controller; a PWM controller is sized on the array short-circuit current (note).
References
- Off-grid PV sizing by energy balance (peak sun hours, autonomy, depth of discharge) (definitions)
Questions and answers
What are peak sun hours?
Daily solar energy on the array expressed as hours at 1 kW/m²: 4–6 in most of India, lowest in the monsoon.
Why only 50 % depth of discharge?
Lead-acid batteries last much longer when cycled shallowly; lithium batteries allow 80–90 %.
What do the defaults represent?
A 5 kWh/day load on a 48 V system with 4.5 peak sun hours and two days' autonomy.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.