Worked example
Example: 220 kV overhead. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Line voltage | 220.00 kV |
| Inductance (mH/km) | 1.0000 - |
| Capacitance (nF/km) | 11.500 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Surge impedance | 294.88 Ω |
| Surge impedance loading | 164.13 MW |
| Wave velocity | 294,884 km/s |
Open this example in the calculator and change any input.
Formula
\(Z_c = \sqrt{\frac{L'}{C'}}, \quad SIL = \frac{V^2}{Z_c}, \quad v_w = \frac{1}{\sqrt{L'C'}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V\) | Line voltage | V |
| \(L'\) | Inductance (mH/km) | - |
| \(C'\) | Capacitance (nF/km) | - |
| \(Z_c\) | Surge impedance | Ω |
| \(SIL\) | Surge impedance loading | W |
| \(v_w\) | Wave velocity | m/s |
Method and standards
Lossless line.
Where it is used
- Line loadability studies.
- Reactive compensation planning.
Common mistakes
- Using phase voltage in SIL.
- Per-km values in the wrong units.
Assumptions and limits
Lossless line (R and G neglected). L' is entered in mH/km and C' in nF/km; the page warns if their product gives a wave velocity above the speed of light, which means the two values are inconsistent.
Lossless line.
References
- Stevenson and Grainger
- Power System Analysis (McGraw-Hill, 1994); Kothari and Nagrath
- Modern Power System Analysis
- 4th ed. (2011) (Z_c = √(L/C), SIL = V²/Z_c)
Questions and answers
What does loading above SIL mean?
The line absorbs reactive power and voltage sags along it; below SIL it generates reactive power and voltage rises.
Why are cables so different?
Their high capacitance gives low surge impedance and a very high SIL; they are always lightly loaded relative to it.
What do the defaults represent?
A 220 kV overhead line with 1 mH/km and 11.5 nF/km.