Worked example
Example: Illustrative bolted fault, H = 5 s. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Mechanical power (pu) | 0.80000 - |
| Peak electrical power before the fault (pu) | 1.8000 - |
| Peak power during the fault as a share of P_max | 0 % |
| Peak power after clearing as a share of P_max | 80.000 % |
| Inertia constant | 5.0000 s |
| System frequency | 50.000 Hz |
Applying the formula below gives:
| Result | Value |
|---|---|
| Initial rotor angle | 26.388 ° |
| Largest angle after clearing | 146.25 ° |
| Critical clearing angle | 70.686 ° |
| Critical clearing time | 248.04 ms |
Open this example in the calculator and change any input.
Formula
\(\cos\delta_c = \frac{P_m(\delta_{max} - \delta_0) + r_2P_{max}\cos\delta_{max} - r_1P_{max}\cos\delta_0}{(r_2 - r_1)P_{max}}, \quad \frac{2H}{\omega_s}\frac{d^2\delta}{dt^2} = P_m - P_e\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(P_m\) | Mechanical power (pu) | - |
| \(P_{max}\) | Peak electrical power before the fault (pu) | - |
| \(r_1\) | Peak power during the fault as a share of P_max | - |
| \(r_2\) | Peak power after clearing as a share of P_max | - |
| \(H\) | Inertia constant | s |
| \(f\) | System frequency | 1/s |
| \(\delta_0\) | Initial rotor angle | rad |
| \(\delta_{max}\) | Largest angle after clearing | rad |
| \(\delta_c\) | Critical clearing angle | rad |
| \(t_c\) | Critical clearing time | s |
Method and standards
Equal-area criterion.
Where it is used
- Checking protection clearing times for generators.
- Teaching transient stability.
Common mistakes
- Using the pre-fault power curve after clearing.
- Mixing H on different MVA bases.
Assumptions and limits
- Single machine on an infinite bus; classical model; no damping.
References
- Equal-area criterion and the classical swing equation
Questions and answers
What is the critical clearing time?
The longest a fault may last before the generator loses synchronism; protection must clear faster.
Why does inertia help?
A larger H slows the rotor's acceleration during the fault, so the critical angle is reached later.
What do the defaults represent?
An illustrative generator sending 0.8 pu with 1.8 pu peak transfer, a bolted fault, 0.8 of the transfer after clearing, H = 5 s, 50 Hz.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Kundur, Power System Stability and Control (McGraw-Hill, 1994), Grainger and Stevenson, Power System Analysis (McGraw-Hill, 1994)