Worked example
Example: Illustrative three loads at 415 V. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Line-to-line voltage | 415.00 V |
| Load 1 power | 50.000 kW |
| Load 1 power factor (negative = leading) | 0.80000 - |
| Load 2 power | 30.000 kW |
| Load 2 power factor | 0.90000 - |
| Load 3 power | 20.000 kW |
| Load 3 power factor | 1.0000 - |
| Load 4 power | 0 kW |
| Load 4 power factor | 0.85000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Total real power | 100.00 kW |
| Total reactive power (+ lagging) | 52.030 kvar |
| Total apparent power | 112.73 kVA |
| Overall power factor | 0.88711 |
| Line current | 156.82 A |
Open this example in the calculator and change any input.
Formula
\(P = \sum P_k, \quad Q = \sum P_k\tan\varphi_k, \quad pf = \frac{P}{\sqrt{P^2 + Q^2}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V\) | Line-to-line voltage | V |
| \(P_1\) | Load 1 power | W |
| \(pf_1\) | Load 1 power factor (negative = leading) | - |
| \(P_2\) | Load 2 power | W |
| \(pf_2\) | Load 2 power factor | - |
| \(P_3\) | Load 3 power | W |
| \(pf_3\) | Load 3 power factor | - |
| \(P_4\) | Load 4 power | W |
| \(pf_4\) | Load 4 power factor | - |
| \(P\) | Total real power | W |
| \(Q\) | Total reactive power (+ lagging) | var |
| \(S\) | Total apparent power | VA |
| \(pf\) | Overall power factor | - |
| \(I\) | Line current | A |
Method and standards
Power summation.
Where it is used
- Board and transformer loading.
- Power factor correction studies.
Common mistakes
- Averaging power factors.
- Forgetting the sign of leading loads.
Assumptions and limits
- Balanced three-phase loads at one voltage.
References
- Power triangle summation
Questions and answers
Can I average the power factors?
No: power factors combine through reactive power, weighted by each load's kW; a simple average is wrong.
What does a leading load do?
Its negative reactive power offsets lagging loads, as a capacitor bank does.
What do the defaults represent?
An illustrative 415 V board with 50 kW at 0.8, 30 kW at 0.9 and 20 kW resistive load.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Grainger and Stevenson, Power System Analysis (McGraw-Hill, 1994)