Feeder Voltage Rise from Distributed Generation

Approximate voltage rise at the point of connection of a generator exporting real and reactive power through a feeder of given resistance and reactance.

Thermal power plant

Inputs

Examples: Illustrative 3 MW at 11 kV, unity power factorAbsorbing 1 MvarRural 33 kV line 10 MWResistive LV cable, no reactance

Accepted: 0.1 to 1,000 kV
Accepted: 0 to 1,000 MW
Accepted: -1,000 to 1,000 Mvar
Accepted: 0 to 1,000 Ω
Accepted: 0 to 1,000 Ω

Results

ΔV ≈ (PR + QX)/V (three-phase quantities, line-to-line voltage). On rural feeders with high R/X, absorbing reactive power helps little and export may need curtailment or network reinforcement.

Voltage rise545.45V
Voltage rise4.9587%
Reactive power to cancel the rise-2.0000Mvar
Power factor that gives no rise0.83205

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 3 MW at 11 kV, unity power factor. The inputs, in the units selected above:

InputValue
Nominal line-to-line voltage11.000 kV
Real power exported3.0000 MW
Reactive power exported (negative = absorbed)0 Mvar
Feeder resistance2.0000 Ω
Feeder reactance3.0000 Ω

Applying the formula below gives:

ResultValue
Voltage rise545.45 V
Voltage rise4.9587 %
Reactive power to cancel the rise-2.0000 Mvar
Power factor that gives no rise0.83205

Open this example in the calculator and change any input.

Formula

\(\Delta V \approx \frac{PR + QX}{V}, \quad Q_0 = -\frac{PR}{X}\)

Variables

Symbol Meaning SI unit
\(V\) Nominal line-to-line voltage V
\(P\) Real power exported W
\(Q\) Reactive power exported (negative = absorbed) var
\(R\) Feeder resistance Ω
\(X\) Feeder reactance Ω
\(\Delta V\) Voltage rise V
\(\Delta V/V\) Voltage rise -
\(Q_0\) Reactive power to cancel the rise var
\(pf_0\) Power factor that gives no rise -

Method and standards

Voltage rise.

Where it is used

  • Grid connection studies for solar and wind.
  • Setting inverter power-factor modes.

Common mistakes

  • Using phase voltage with three-phase power.
  • Ignoring load on the feeder at minimum demand.

Assumptions and limits

  • Short line; small angle; constant source voltage.

References

  • Approximate voltage drop/rise on a feeder

Questions and answers

Why does solar raise feeder voltage?

Exporting current flows back through the feeder impedance, so the voltage at the generator rises above the substation voltage.

Can inverters fix it?

Partly, by absorbing reactive power; on cables with high R/X the effect is small, and active power limits or reinforcement are needed.

What do the defaults represent?

An illustrative 3 MW solar farm exporting at unity power factor into an 11 kV feeder with 2 Ω resistance and 3 Ω reactance.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Gilbert Masters, Renewable and Efficient Electric Power Systems (Wiley, 2004), ch. 3

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.