Worked example
Example: Illustrative 480 V 60 kVA at 0.8 lagging. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Rated line voltage (star) | 480.00 V |
| Load apparent power | 60.000 kVA |
| Power factor angle (+ lagging, − leading) | 36.870 ° |
| Armature resistance per phase | 0.015000 Ω |
| Synchronous reactance per phase | 0.10000 Ω |
Applying the formula below gives:
| Result | Value |
|---|---|
| Armature current | 72.169 A |
| Internal EMF per phase | 282.37 V |
| Torque angle | 1.0398 ° |
| Voltage regulation | 1.8918 % |
Open this example in the calculator and change any input.
Formula
\(E_A = V_\phi + (R_A + jX_s)I_A, \quad VR = \frac{E_A - V_\phi}{V_\phi}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V_L\) | Rated line voltage (star) | V |
| \(S\) | Load apparent power | VA |
| \(\varphi\) | Power factor angle (+ lagging, − leading) | rad |
| \(R_A\) | Armature resistance per phase | Ω |
| \(X_s\) | Synchronous reactance per phase | Ω |
| \(I_A\) | Armature current | A |
| \(E_A\) | Internal EMF per phase | V |
| \(\delta\) | Torque angle | rad |
| \(VR\) | Voltage regulation | - |
Method and standards
Regulation.
Where it is used
- Alternator selection and AVR range checks.
- Teaching synchronous machine phasors.
Common mistakes
- Mixing line and phase voltages.
- Wrong sign of the power factor angle.
Assumptions and limits
- Round rotor; unsaturated; star connection; balanced load.
References
- Synchronous impedance (EMF) method
Questions and answers
Why is regulation worse for lagging loads?
Lagging current's reactive drop across X_s directly opposes the terminal voltage, so more EMF is needed.
Can regulation be negative?
Yes, with leading (capacitive) loads the reactive drop adds to the terminal voltage.
What do the defaults represent?
An illustrative 480 V, 60 kVA generator at 0.8 power factor lagging with R_A 0.015 Ω and X_s 0.1 Ω per phase.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Chapman, Electric Machinery Fundamentals, 5th ed. (McGraw-Hill, 2012)