Loss Factor from Load Factor and Annual Energy Losses

Load factor of a feeder or transformer from peak load and annual energy, the loss factor by the Buller-Woodrow relation and the annual energy lost from peak losses.

Thermal power plant

Inputs

Examples: Illustrative 2 MW peak feeder, 9000 MWhIndustrial flat load LF 0.8Residential peaky LF 0.35

Accepted: 0.001 to 10,000,000 kW
Accepted: 0.001 to 27,778,000 MWh
Accepted: 0 to 1,000,000 kW
Accepted: 0 to 1

Results

LsF = k·LF + (1 − k)·LF² (Buller–Woodrow); copper losses scale with the square of load, so the loss factor is lower than the load factor. Add no-load (iron) losses separately at 8,760 hours.

Load factor51.370%
Loss factor33.883%
Annual energy losses178.09MWh
Equivalent full-loss hours2,968.2h
Losses as a share of energy delivered1.9788%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 2 MW peak feeder, 9000 MWh. The inputs, in the units selected above:

InputValue
Peak load2,000.0 kW
Annual energy delivered9,000.0 MWh
Load losses at peak60.000 kW
Loss factor coefficient (0.15–0.3)0.30000 -

Applying the formula below gives:

ResultValue
Load factor51.370 %
Loss factor33.883 %
Annual energy losses178.09 MWh
Equivalent full-loss hours2,968.2 h
Losses as a share of energy delivered1.9788 %

Open this example in the calculator and change any input.

Formula

\(LF = \frac{E}{P_{pk}\cdot 8760}, \quad LsF = k\,LF + (1 - k)LF^2, \quad E_L = P_{L,pk}\,LsF\cdot 8760\)

Variables

Symbol Meaning SI unit
\(P_{pk}\) Peak load W
\(E\) Annual energy delivered J
\(P_{L,pk}\) Load losses at peak W
\(k\) Loss factor coefficient (0.15–0.3) -
\(LF\) Load factor -
\(LsF\) Loss factor -
\(E_L\) Annual energy losses J
\(h_{eq}\) Equivalent full-loss hours s
\(E_L/E\) Losses as a share of energy delivered -

Method and standards

Loss factor estimate.

Where it is used

  • Network loss studies and cable or transformer economics.
  • Loss allocation.

Common mistakes

  • Multiplying peak losses by the load factor.
  • Forgetting no-load losses.

Assumptions and limits

  • Empirical relation; annual basis.

References

  • Loss factor (Buller–Woodrow)

Questions and answers

Why is the loss factor below the load factor?

Losses vary with the square of current; hours at low load contribute very little loss, so average loss is less than average load would suggest.

What k should I use?

About 0.15–0.2 for distribution feeders and 0.3 for transmission; fit it to metered data where possible.

What do the defaults represent?

An illustrative 2 MW peak feeder delivering 9,000 MWh a year with 60 kW of load losses at peak and k = 0.3.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Gilbert Masters, Renewable and Efficient Electric Power Systems (Wiley, 2004), ch. 3

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.