Synchronous Generator Short-Circuit Ratio

Short-circuit ratio of a synchronous generator from its open-circuit and short-circuit characteristics, the saturated synchronous reactance and its value in ohms.

Inputs

Examples: Illustrative 50 MVA, 11 kVHydro generator, high SCRTurbogenerator 500 MVA

Accepted: 0.1 to 10,000 A
Accepted: 0.1 to 10,000 A
Accepted: 0.1 to 50 kV
Accepted: 0.001 to 2,000 MVA

Results

SCR = field current for rated voltage at no load ÷ field current for rated armature current on a sustained three-phase short circuit. It equals the reciprocal of the saturated synchronous reactance in per unit. A high SCR (0.8–1.2 for hydro generators) means a stiffer, larger and more stable machine; turbogenerators are often 0.4–0.7. The sustained short-circuit current at that field is SCR × rated current.

Short-circuit ratio0.68852
Saturated synchronous reactance (per unit)1.4524
Base impedance2.4200Ω
Saturated synchronous reactance3.5148Ω
Sustained short-circuit current at the rated-voltage field1,806.9A

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 50 MVA, 11 kV. The inputs, in the units selected above:

InputValue
Field current for rated voltage on open circuit420.00 A
Field current for rated current on short circuit610.00 A
Rated line voltage11.000 kV
Rated apparent power50.000 MVA

Applying the formula below gives:

ResultValue
Short-circuit ratio0.68852
Saturated synchronous reactance (per unit)1.4524
Base impedance2.4200 Ω
Saturated synchronous reactance3.5148 Ω
Sustained short-circuit current at the rated-voltage field1,806.9 A

Open this example in the calculator and change any input.

Formula

\(SCR = \frac{I_{F,oc}}{I_{F,sc}}, \quad X_{s,sat} = \frac{1}{SCR}\ \text{pu}, \quad Z_b = \frac{V_L^2}{S_n}\)

Variables

Symbol Meaning SI unit
\(I_{F,oc}\) Field current for rated voltage on open circuit A
\(I_{F,sc}\) Field current for rated current on short circuit A
\(V_L\) Rated line voltage V
\(S_n\) Rated apparent power VA
\(SCR\) Short-circuit ratio -
\(X_{s,sat}\) Saturated synchronous reactance (per unit) -
\(Z_b\) Base impedance Ω
\(I_{sc}\) Sustained short-circuit current at the rated-voltage field A

Method and standards

Short-circuit ratio.

Where it is used

  • Generator specification and acceptance testing.
  • Stability studies.

Common mistakes

  • Using the air-gap line instead of the OCC.
  • Mixing per-phase and line quantities.

Assumptions and limits

  • Steady-state short circuit; three-phase balanced test.

References

  • Open- and short-circuit characteristics

Questions and answers

Why does SCR matter?

It shows how strongly the generator holds voltage and stays in step; higher SCR means more stability margin but a bigger machine.

Why is the reactance 'saturated'?

The open-circuit point is on the saturated part of the magnetisation curve, lowering the effective reactance.

What do the defaults represent?

An illustrative 50 MVA, 11 kV generator needing 420 A field at rated voltage and 610 A for rated short-circuit current.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Chapman, Electric Machinery Fundamentals, 5th ed. (McGraw-Hill, 2012), Kundur, Power System Stability and Control (McGraw-Hill, 1994)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.