Worked example
Example: Illustrative 50 MVA, 11 kV. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Field current for rated voltage on open circuit | 420.00 A |
| Field current for rated current on short circuit | 610.00 A |
| Rated line voltage | 11.000 kV |
| Rated apparent power | 50.000 MVA |
Applying the formula below gives:
| Result | Value |
|---|---|
| Short-circuit ratio | 0.68852 |
| Saturated synchronous reactance (per unit) | 1.4524 |
| Base impedance | 2.4200 Ω |
| Saturated synchronous reactance | 3.5148 Ω |
| Sustained short-circuit current at the rated-voltage field | 1,806.9 A |
Open this example in the calculator and change any input.
Formula
\(SCR = \frac{I_{F,oc}}{I_{F,sc}}, \quad X_{s,sat} = \frac{1}{SCR}\ \text{pu}, \quad Z_b = \frac{V_L^2}{S_n}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(I_{F,oc}\) | Field current for rated voltage on open circuit | A |
| \(I_{F,sc}\) | Field current for rated current on short circuit | A |
| \(V_L\) | Rated line voltage | V |
| \(S_n\) | Rated apparent power | VA |
| \(SCR\) | Short-circuit ratio | - |
| \(X_{s,sat}\) | Saturated synchronous reactance (per unit) | - |
| \(Z_b\) | Base impedance | Ω |
| \(I_{sc}\) | Sustained short-circuit current at the rated-voltage field | A |
Method and standards
Short-circuit ratio.
Where it is used
- Generator specification and acceptance testing.
- Stability studies.
Common mistakes
- Using the air-gap line instead of the OCC.
- Mixing per-phase and line quantities.
Assumptions and limits
- Steady-state short circuit; three-phase balanced test.
References
- Open- and short-circuit characteristics
Questions and answers
Why does SCR matter?
It shows how strongly the generator holds voltage and stays in step; higher SCR means more stability margin but a bigger machine.
Why is the reactance 'saturated'?
The open-circuit point is on the saturated part of the magnetisation curve, lowering the effective reactance.
What do the defaults represent?
An illustrative 50 MVA, 11 kV generator needing 420 A field at rated voltage and 610 A for rated short-circuit current.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.