Worked example
Example: Illustrative factory month. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Energy used in the month | 150,000 kWh |
| Recorded maximum demand | 400.00 kVA |
| Contract demand | 500.00 kVA |
| Minimum billing demand as a share of contract demand | 75.000 % |
| Demand rate per kVA per month | 400.00 - |
| Energy rate per kWh | 7.0000 - |
| Hours in the billing month | 720.00 h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Billing demand | 400.00 kVA |
| Demand charge | 160,000 |
| Energy charge | 1,050,000 |
| Demand plus energy charge | 1,210,000 |
| Average cost per kWh | 8.0667 |
| Load factor (kWh over MD × hours) | 52.083 % |
| Demand above contract | 0 kVA |
Open this example in the calculator and change any input.
Formula
\(BD = \max(MD,\ f_m CD), \quad C = r_d BD + r_e E, \quad LF = \frac{E}{MD\cdot t}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(E\) | Energy used in the month | J |
| \(MD\) | Recorded maximum demand | VA |
| \(CD\) | Contract demand | VA |
| \(f_m\) | Minimum billing demand as a share of contract demand | - |
| \(r_d\) | Demand rate per kVA per month | - |
| \(r_e\) | Energy rate per kWh | - |
| \(t\) | Hours in the billing month | s |
| \(BD\) | Billing demand | VA |
| \(C_d\) | Demand charge | - |
| \(C_e\) | Energy charge | - |
| \(C\) | Demand plus energy charge | - |
| \(c\) | Average cost per kWh | - |
| \(LF\) | Load factor (kWh over MD × hours) | - |
| \(\Delta S\) | Demand above contract | VA |
Method and standards
Electricity bill.
Where it is used
- Industrial and commercial HT consumers.
- Deciding on contract demand changes.
Common mistakes
- Comparing load factors on kW and kVA.
- Ignoring the minimum billing demand when reducing load.
Assumptions and limits
- Simple two-part tariff; no taxes or rebates.
References
- Two-part tariff arithmetic
Questions and answers
What is billing demand?
The higher of the recorded maximum demand and the minimum share (often 75–85 %) of contract demand.
How does load factor affect cost per unit?
At the defaults the load factor is 52 % and the average cost is about 8.07 per kWh against an energy rate of 7.
What do the defaults represent?
An illustrative factory using 150,000 kWh a month with 400 kVA maximum demand on a 500 kVA contract, 75 % minimum billing, demand rate 400 per kVA and energy rate 7 per kWh.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.