Worked example
Example: Illustrative 75 kW DOL, 15 % dip. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Motor rated output | 75.000 kW |
| Motor efficiency | 93.000 % |
| Motor running power factor | 86.000 % |
| Locked-rotor current / rated current | 6.5000 - |
| Starter kVA factor (DOL 1, star-delta 0.33, soft start about 0.5) | 100.00 % |
| Generator subtransient reactance (per unit) | 0.15000 - |
| Allowed voltage dip | 15.000 % |
| Planned running load (share of rating) | 80.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Motor running kVA | 93.773 kVA |
| Motor starting kVA | 609.53 kVA |
| Generator kVA for the dip limit | 518.10 kVA |
| Generator kVA for running | 117.22 kVA |
| Generator kVA needed | 518.10 kVA |
Open this example in the calculator and change any input.
Formula
\(S_s = k_{LR}k_s\frac{P_m}{\eta\,pf}, \quad S_g = \max\left(X''_dS_s\frac{1 - \Delta V}{\Delta V},\;\frac{S_r}{\lambda}\right)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(P_m\) | Motor rated output | W |
| \(\eta\) | Motor efficiency | - |
| \(pf\) | Motor running power factor | - |
| \(k_{LR}\) | Locked-rotor current / rated current | - |
| \(k_s\) | Starter kVA factor (DOL 1, star-delta 0.33, soft start about 0.5) | - |
| \(X''_d\) | Generator subtransient reactance (per unit) | - |
| \(\Delta V_{max}\) | Allowed voltage dip | - |
| \(\lambda\) | Planned running load (share of rating) | - |
| \(S_r\) | Motor running kVA | VA |
| \(S_s\) | Motor starting kVA | VA |
| \(S_{g,start}\) | Generator kVA for the dip limit | VA |
| \(S_{g,run}\) | Generator kVA for running | VA |
| \(S_g\) | Generator kVA needed | VA |
Method and standards
Motor-start dip.
Where it is used
- Diesel generator selection.
- Standby and island power systems.
Common mistakes
- Sizing only for running kW.
- Ignoring the starter type.
Assumptions and limits
- Single motor start; regulator response ignored.
References
- Voltage dip on a generator from motor starting kVA
Questions and answers
Why does one motor drive generator size?
A direct-on-line start draws about six times running kVA at low power factor; the generator's reactance turns that into a deep voltage dip.
How much does a soft starter help?
It roughly halves starting kVA; a VFD reduces it to near running current, often allowing a much smaller set.
What do the defaults represent?
An illustrative 75 kW motor started direct on line (6.5 × rated current) on a generator with X''_d = 0.15, allowing a 15 % dip.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.