Worked example
Example: Illustrative 2 MW peak feeder, 9000 MWh. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Peak load | 2,000.0 kW |
| Annual energy delivered | 9,000.0 MWh |
| Load losses at peak | 60.000 kW |
| Loss factor coefficient (0.15–0.3) | 0.30000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Load factor | 51.370 % |
| Loss factor | 33.883 % |
| Annual energy losses | 178.09 MWh |
| Equivalent full-loss hours | 2,968.2 h |
| Losses as a share of energy delivered | 1.9788 % |
Open this example in the calculator and change any input.
Formula
\(LF = \frac{E}{P_{pk}\cdot 8760}, \quad LsF = k\,LF + (1 - k)LF^2, \quad E_L = P_{L,pk}\,LsF\cdot 8760\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(P_{pk}\) | Peak load | W |
| \(E\) | Annual energy delivered | J |
| \(P_{L,pk}\) | Load losses at peak | W |
| \(k\) | Loss factor coefficient (0.15–0.3) | - |
| \(LF\) | Load factor | - |
| \(LsF\) | Loss factor | - |
| \(E_L\) | Annual energy losses | J |
| \(h_{eq}\) | Equivalent full-loss hours | s |
| \(E_L/E\) | Losses as a share of energy delivered | - |
Method and standards
Loss factor estimate.
Where it is used
- Network loss studies and cable or transformer economics.
- Loss allocation.
Common mistakes
- Multiplying peak losses by the load factor.
- Forgetting no-load losses.
Assumptions and limits
- Empirical relation; annual basis.
References
- Loss factor (Buller–Woodrow)
Questions and answers
Why is the loss factor below the load factor?
Losses vary with the square of current; hours at low load contribute very little loss, so average loss is less than average load would suggest.
What k should I use?
About 0.15–0.2 for distribution feeders and 0.3 for transmission; fit it to metered data where possible.
What do the defaults represent?
An illustrative 2 MW peak feeder delivering 9,000 MWh a year with 60 kW of load losses at peak and k = 0.3.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Gilbert Masters, Renewable and Efficient Electric Power Systems (Wiley, 2004), ch. 3