Worked example
Example: Illustrative 100 MVA at 70 MW. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Rated apparent power | 100.00 MVA |
| Rated power factor (lagging) | 85.000 % |
| Synchronous reactance (per unit) | 1.8000 - |
| Terminal voltage (per unit) | 1.0000 - |
| Real power output | 70.000 MW |
Applying the formula below gives:
| Result | Value |
|---|---|
| Maximum internal EMF (per unit, rated field) | 2.4772 |
| Stator-current limit | 71.414 Mvar |
| Field-current limit | 62.933 Mvar |
| Maximum reactive power (lagging) | 62.933 Mvar |
| Minimum reactive power (leading) | -55.556 Mvar |
Open this example in the calculator and change any input.
Formula
\(E_{max} = \left|V + jX_sI_n\right|, \quad Q_{field} = \sqrt{\left(\frac{V_tE_{max}}{X_s}\right)^2 - P^2} - \frac{V_t^2}{X_s}, \quad Q_{stator} = \sqrt{V_t^2 - P^2}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(S_n\) | Rated apparent power | VA |
| \(\cos\varphi_n\) | Rated power factor (lagging) | - |
| \(X_s\) | Synchronous reactance (per unit) | - |
| \(V_t\) | Terminal voltage (per unit) | - |
| \(P\) | Real power output | W |
| \(E_{max}\) | Maximum internal EMF (per unit, rated field) | - |
| \(Q_{stator}\) | Stator-current limit | var |
| \(Q_{field}\) | Field-current limit | var |
| \(Q_{max}\) | Maximum reactive power (lagging) | var |
| \(Q_{min}\) | Minimum reactive power (leading) | var |
Method and standards
Capability.
Where it is used
- Operating limits for plant generators.
- Grid code reactive power studies.
Common mistakes
- Ignoring the field limit at low power factor.
- Using salient-pole machines with this round-rotor model.
Assumptions and limits
- Round rotor; no saturation; resistance neglected; per-unit on rated MVA.
References
- Round-rotor capability diagram
Questions and answers
Why is lagging reactive power limited more at low load?
There the field (rotor) heating limit, not the stator, is reached first because high excitation is needed.
Why is leading operation limited?
Low excitation weakens the magnetic coupling, risking loss of synchronism, and heats the stator core ends.
What do the defaults represent?
An illustrative 100 MVA, 0.85 PF generator with X_s 1.8 per unit at 1.0 per unit voltage delivering 70 MW.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Kundur, Power System Stability and Control (McGraw-Hill, 1994), Chapman, Electric Machinery Fundamentals, 5th ed. (McGraw-Hill, 2012)