Synchronous Generator Capability: Reactive Power Limits

Maximum and minimum reactive power of a round-rotor generator at a real power from its stator current, field current and steady-state stability limits.

Inputs

Examples: Illustrative 100 MVA at 70 MWSame unit at 30 MW (field limit)Industrial 12.5 MVA, 0.8 PF at full load

Accepted: 0.01 to 2,000 MVA
Accepted: 50 to 100 %
Accepted: 0.3 to 4
Accepted: 0.8 to 1.2
Accepted: 0 to 2,000 MW

Results

Per unit on the rated MVA. Stator heating limits S = V_tI ≤ V_t (a circle about the origin). Rotor heating limits E to its rated-point value E_max = |V + jX_sI_n|, a circle of radius V_tE_max/X_s centred at Q = −V_t²/X_s. The field limit governs at low power factor lagging; the stator limit near rated power. Leading operation is limited here by the theoretical steady-state stability limit Q = −V_t²/X_s and by stator current; real machines also have end-core heating and practical stability margins, and turbine power caps P.

Maximum internal EMF (per unit, rated field)2.4772
Stator-current limit71.414Mvar
Field-current limit62.933Mvar
Maximum reactive power (lagging)62.933Mvar
Minimum reactive power (leading)-55.556Mvar

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 100 MVA at 70 MW. The inputs, in the units selected above:

InputValue
Rated apparent power100.00 MVA
Rated power factor (lagging)85.000 %
Synchronous reactance (per unit)1.8000 -
Terminal voltage (per unit)1.0000 -
Real power output70.000 MW

Applying the formula below gives:

ResultValue
Maximum internal EMF (per unit, rated field)2.4772
Stator-current limit71.414 Mvar
Field-current limit62.933 Mvar
Maximum reactive power (lagging)62.933 Mvar
Minimum reactive power (leading)-55.556 Mvar

Open this example in the calculator and change any input.

Formula

\(E_{max} = \left|V + jX_sI_n\right|, \quad Q_{field} = \sqrt{\left(\frac{V_tE_{max}}{X_s}\right)^2 - P^2} - \frac{V_t^2}{X_s}, \quad Q_{stator} = \sqrt{V_t^2 - P^2}\)

Variables

Symbol Meaning SI unit
\(S_n\) Rated apparent power VA
\(\cos\varphi_n\) Rated power factor (lagging) -
\(X_s\) Synchronous reactance (per unit) -
\(V_t\) Terminal voltage (per unit) -
\(P\) Real power output W
\(E_{max}\) Maximum internal EMF (per unit, rated field) -
\(Q_{stator}\) Stator-current limit var
\(Q_{field}\) Field-current limit var
\(Q_{max}\) Maximum reactive power (lagging) var
\(Q_{min}\) Minimum reactive power (leading) var

Method and standards

Capability.

Where it is used

  • Operating limits for plant generators.
  • Grid code reactive power studies.

Common mistakes

  • Ignoring the field limit at low power factor.
  • Using salient-pole machines with this round-rotor model.

Assumptions and limits

  • Round rotor; no saturation; resistance neglected; per-unit on rated MVA.

References

  • Round-rotor capability diagram

Questions and answers

Why is lagging reactive power limited more at low load?

There the field (rotor) heating limit, not the stator, is reached first because high excitation is needed.

Why is leading operation limited?

Low excitation weakens the magnetic coupling, risking loss of synchronism, and heats the stator core ends.

What do the defaults represent?

An illustrative 100 MVA, 0.85 PF generator with X_s 1.8 per unit at 1.0 per unit voltage delivering 70 MW.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Kundur, Power System Stability and Control (McGraw-Hill, 1994), Chapman, Electric Machinery Fundamentals, 5th ed. (McGraw-Hill, 2012)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.