Worked example
Example: Illustrative two units for 400 MW. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Unit 1 linear cost coefficient (per MWh) | 7.0000 - |
| Unit 1 quadratic coefficient (per MW²h) | 0.008000 - |
| Unit 2 linear cost coefficient (per MWh) | 7.5000 - |
| Unit 2 quadratic coefficient (per MW²h) | 0.009600 - |
| Demand | 400.00 MW |
| Unit 1 minimum | 50.000 MW |
| Unit 1 maximum | 250.00 MW |
| Unit 2 minimum | 50.000 MW |
| Unit 2 maximum | 250.00 MW |
Applying the formula below gives:
| Result | Value |
|---|---|
| Unit 1 output | 232.39 MW |
| Unit 2 output | 167.61 MW |
| System incremental cost (per MWh) | 10.718 |
| Variable fuel cost per hour | 3,585.5 |
Open this example in the calculator and change any input.
Formula
\(\frac{dF_i}{dP_i} = b_i + 2c_iP_i = \lambda, \quad P_1 + P_2 = P_D\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(b_1\) | Unit 1 linear cost coefficient (per MWh) | - |
| \(c_1\) | Unit 1 quadratic coefficient (per MW²h) | - |
| \(b_2\) | Unit 2 linear cost coefficient (per MWh) | - |
| \(c_2\) | Unit 2 quadratic coefficient (per MW²h) | - |
| \(P_D\) | Demand | W |
| \(P_{1,min}\) | Unit 1 minimum | W |
| \(P_{1,max}\) | Unit 1 maximum | W |
| \(P_{2,min}\) | Unit 2 minimum | W |
| \(P_{2,max}\) | Unit 2 maximum | W |
| \(P_1\) | Unit 1 output | W |
| \(P_2\) | Unit 2 output | W |
| \(\lambda\) | System incremental cost (per MWh) | - |
| \(F\) | Variable fuel cost per hour | - |
Method and standards
Economic dispatch.
Where it is used
- Captive and cogeneration plants with several units.
- Teaching power system operation.
Common mistakes
- Including fixed costs in the incremental cost.
- Ignoring unit limits.
Assumptions and limits
- Quadratic cost curves; no losses; both units running.
References
- Equal incremental cost rule with unit limits
Questions and answers
Why equal incremental costs?
If one unit's incremental cost were lower, moving load to it would cut total cost; the optimum is reached when no such move helps.
What happens at a unit limit?
That unit stays at its limit and the others share the rest at equal incremental cost.
What do the defaults represent?
Two illustrative units with costs 7.0 + 0.016P and 7.5 + 0.0192P per MWh supplying 400 MW.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Grainger and Stevenson, Power System Analysis (McGraw-Hill, 1994)