Worked example
Example: Illustrative 480 V motor, 0.8 leading. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Line voltage (star) | 480.00 V |
| Input power | 80.000 kW |
| Power factor | 80.000 % |
| Leading (+1) or lagging (−1) | 1.0000 - |
| Synchronous reactance per phase | 2.5000 Ω |
| Armature resistance per phase | 0 Ω |
| Phase EMF on the OCC | 277.00 V |
| Field current for that EMF | 4.0000 A |
Applying the formula below gives:
| Result | Value |
|---|---|
| Armature current | 120.28 A |
| Internal EMF per phase | 516.94 V |
| Torque angle | 27.734 ° |
| Field current needed | 7.4648 A |
| Reactive power (+ supplied to the system) | 60.000 kvar |
Open this example in the calculator and change any input.
Formula
\(E_A = V_\phi - (R_A + jX_s)I_A, \quad I_F = I_{F0}\frac{E_A}{E_0}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V_L\) | Line voltage (star) | V |
| \(P\) | Input power | W |
| \(\cos\varphi\) | Power factor | - |
| \(\pm\) | Leading (+1) or lagging (−1) | - |
| \(X_s\) | Synchronous reactance per phase | Ω |
| \(R_A\) | Armature resistance per phase | Ω |
| \(E_0\) | Phase EMF on the OCC | V |
| \(I_{F0}\) | Field current for that EMF | A |
| \(I_A\) | Armature current | A |
| \(E_A\) | Internal EMF per phase | V |
| \(\delta\) | Torque angle | rad |
| \(I_F\) | Field current needed | A |
| \(Q\) | Reactive power (+ supplied to the system) | var |
Method and standards
Excitation.
Where it is used
- Power factor correction with synchronous motors.
- Checking field current requirement.
Common mistakes
- Mixing generator and motor sign conventions.
- Using line voltage in per-phase phasors.
Assumptions and limits
- Round rotor; unsaturated OCC; star connection.
References
- Synchronous machine phasor equations
Questions and answers
How does excitation change the power factor?
At fixed load, raising field current raises E_A, swinging the armature current from lagging through unity to leading.
What is the V-curve?
The plot of armature current against field current at constant load: minimum current at unity power factor.
What do the defaults represent?
An illustrative 480 V star motor taking 80 kW at 0.8 leading, X_s 2.5 Ω, with 277 V per phase at 4 A field.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Chapman, Electric Machinery Fundamentals, 5th ed. (McGraw-Hill, 2012)