Worked example
Example: Illustrative: 415 V 15 kW class B motor. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Stator resistance per phase (from the DC test, star equivalent) | 0.25000 Ω |
| No-load line voltage | 415.00 V |
| No-load current | 8.5000 A |
| No-load input power (three-phase) | 900.00 W |
| Locked-rotor line voltage | 85.000 V |
| Locked-rotor current | 28.000 A |
| Locked-rotor input power (three-phase) | 1,900.0 W |
| Locked-rotor test frequency relative to rated | 1.0000 - |
| Design class (split of the leakage reactance) | Class B (X₁ = 0.4 X_LR) |
Applying the formula below gives:
| Result | Value |
|---|---|
| Stator leakage reactance | 0.62216 Ω |
| Rotor leakage reactance referred | 0.93324 Ω |
| Magnetising reactance | 27.566 Ω |
| Rotor resistance referred | 0.59623 Ω |
| Rotational (friction, windage and core) loss | 845.81 W |
| No-load power factor | 0.14730 |
| Locked-rotor impedance per phase | 1.7527 Ω |
Open this example in the calculator and change any input.
Formula
\(|Z_{LR}| = \frac{V_{br}/\sqrt 3}{I_{br}}, \quad R_{LR} = \frac{P_{br}}{3I_{br}^2}, \quad X_{LR} = \frac{f_{rated}}{f_{test}}\sqrt{|Z_{LR}|^2 - R_{LR}^2}\)
\(X_m = \frac{V_{nl}/\sqrt 3}{I_{nl}} - X_1, \quad R'_2 = (R_{LR} - R_1)\left(\frac{X'_2 + X_m}{X_m}\right)^2, \quad P_{rot} = P_{nl} - 3I_{nl}^2R_1\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(R_1\) | Stator resistance per phase (from the DC test, star equivalent) | Ω |
| \(V_{nl}\) | No-load line voltage | V |
| \(I_{nl}\) | No-load current | A |
| \(P_{nl}\) | No-load input power (three-phase) | W |
| \(V_{br}\) | Locked-rotor line voltage | V |
| \(I_{br}\) | Locked-rotor current | A |
| \(P_{br}\) | Locked-rotor input power (three-phase) | W |
| \(f_{test}/f_{rated}\) | Locked-rotor test frequency relative to rated | - |
| \(\text{class}\) | Design class (split of the leakage reactance) | - |
| \(X_1\) | Stator leakage reactance | Ω |
| \(X'_2\) | Rotor leakage reactance referred | Ω |
| \(X_m\) | Magnetising reactance | Ω |
| \(R'_2\) | Rotor resistance referred | Ω |
| \(P_{rot}\) | Rotational (friction, windage and core) loss | W |
| \(\cos\phi_{nl}\) | No-load power factor | - |
| \(|Z_{LR}|\) | Locked-rotor impedance per phase | Ω |
Method and standards
Equivalent-circuit parameters from standard motor tests.
Where it is used
- Motor modelling for starting, drives and protection studies.
- Repair-shop testing and acceptance checks.
Common mistakes
- Using line instead of phase values.
- Using the DC resistance of a delta winding without converting to star.
Assumptions and limits
- Balanced three-phase motor, star-equivalent values, linear magnetics.
References
- No-load
- locked-rotor and DC tests for the per-phase equivalent circuit
Questions and answers
Why test the locked rotor at reduced frequency?
Under normal running the rotor frequency is only a few hertz; testing at about 25 % of rated frequency gives a rotor resistance closer to the running value in deep-bar and double-cage rotors.
How is the leakage reactance split?
By the empirical NEMA design-class ratios: equal for class A and D and wound rotors, 40/60 for class B and 30/70 for class C.
What do the defaults represent?
An illustrative 415 V, 15 kW class B motor: no-load 8.5 A and 900 W, locked rotor 85 V, 28 A and 1,900 W, stator resistance 0.25 Ω per phase.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Chapman, Electric Machinery Fundamentals, 5th ed. (McGraw-Hill, 2012), sec. 6.7