Worked example
Example: Illustrative 415 V 15 kW load. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Line voltage | 415.00 V |
| Frequency | 50.000 Hz |
| No-load (magnetising) current | 12.000 A |
| Load real power | 15.000 kW |
| Load power factor (lagging) | 90.000 % |
| Margin on capacitance | 1.1000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Magnetising reactive power | 8.6256 kvar |
| Load reactive power | 7.2648 kvar |
| Capacitance per phase, delta | 107.69 µF |
| Capacitance per phase, star | 323.06 µF |
Open this example in the calculator and change any input.
Formula
\(Q = k\left(\sqrt3V_LI_0 + P_L\tan\varphi_L\right), \quad C_\Delta = \frac{Q}{3\omega V_L^2}, \quad C_Y = 3C_\Delta\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V_L\) | Line voltage | V |
| \(f\) | Frequency | 1/s |
| \(I_0\) | No-load (magnetising) current | A |
| \(P_L\) | Load real power | W |
| \(\cos\varphi_L\) | Load power factor (lagging) | - |
| \(k\) | Margin on capacitance | - |
| \(Q_m\) | Magnetising reactive power | var |
| \(Q_L\) | Load reactive power | var |
| \(C_\Delta\) | Capacitance per phase, delta | F |
| \(C_Y\) | Capacitance per phase, star | F |
Method and standards
Self-excitation.
Where it is used
- Micro-hydro and small wind induction generators.
- Standby conversions of motors to generators.
Common mistakes
- Using the star formula for a delta bank.
- Ignoring the load's reactive power.
Assumptions and limits
- Rated voltage and frequency; magnetising current at rated voltage.
References
- Reactive power balance of the self-excited induction generator
Questions and answers
Why does an induction generator need capacitors off-grid?
It cannot make its own magnetising current; on the grid the network supplies it, off-grid capacitors must.
Why does voltage collapse with heavy inductive load?
The load takes reactive power the capacitors were supplying to the machine, so excitation falls.
What do the defaults represent?
An illustrative 415 V, 50 Hz machine with 12 A no-load current feeding 15 kW at 0.9 power factor, with a 10 % margin.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Chapman, Electric Machinery Fundamentals, 5th ed. (McGraw-Hill, 2012)