Worked example
Example: Illustrative 22 kW replacement. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Shaft output (load) | 22.000 kW |
| Efficiency of the existing motor at this load | 89.000 % |
| Efficiency of the new motor at this load | 93.500 % |
| Running hours per year | 6,000.0 h |
| Electricity price per kWh | 8.0000 - |
| Price of the new motor (or extra cost) | 150,000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Input power saved | 1.1897 kW |
| Energy saved per year | 7.1381 MWh |
| Cost saved per year | 57,105 |
| Simple payback (years) | 2.6267 |
Open this example in the calculator and change any input.
Formula
\(\Delta P = P\left(\frac1{\eta_1} - \frac1{\eta_2}\right), \quad \Delta C = \Delta P\,t\,c, \quad t_{pb} = \frac{C_m}{\Delta C}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(P\) | Shaft output (load) | W |
| \(\eta_1\) | Efficiency of the existing motor at this load | - |
| \(\eta_2\) | Efficiency of the new motor at this load | - |
| \(t\) | Running hours per year | s |
| \(c\) | Electricity price per kWh | - |
| \(C_m\) | Price of the new motor (or extra cost) | - |
| \(\Delta P\) | Input power saved | W |
| \(\Delta E\) | Energy saved per year | J |
| \(\Delta C\) | Cost saved per year | - |
| \(t_{pb}\) | Simple payback (years) | - |
Method and standards
Motor payback.
Where it is used
- Motor replacement programmes.
- Choosing between rewinding and replacing.
Common mistakes
- Using nameplate efficiency of an old motor.
- Ignoring the speed change on centrifugal loads.
Assumptions and limits
- Same shaft output; constant tariff.
References
- Input-power difference at equal output
- Bureau of Energy Efficiency
- Energy Efficiency in Electrical Utilities (Guide Book 3)
Questions and answers
How much does a 22 kW IE3 motor save over an old one?
From 89 % to 93.5 % efficiency at full load, about 1.2 kW, or 7.1 MWh a year at 6,000 h.
Does a more efficient motor always save energy?
Not on fans and pumps if its higher speed raises the load; check the speed.
What do the defaults represent?
An illustrative 22 kW load moved from an 89 % to a 93.5 % efficient motor, 6,000 h a year at 8 per kWh, new motor 150,000.