Soft Starter Current Limit: Motor Torque and Start Time

Motor torque at a soft starter's current limit, the resulting voltage, acceleration time with a load, and the lowest current limit that still starts the load.

Inputs

Examples: Illustrative 110 kW pump motor at 3.5 xFan, low limit 3 xLoaded conveyor at 4.5 x

Accepted: 1 to 1,000,000 N·m
Accepted: 2 to 10
Accepted: 0.3 to 4
Accepted: 1 to 8
Accepted: 0 to 150 %
Accepted: 0.01 to 100,000 kg·m²
Accepted: 95.493 to 3,819.7 rpm

Results

A soft starter lowers the voltage; induction motor current falls in proportion to voltage and torque with its square. Holding current at k × I_n therefore gives about U/U_n = k/(I_LR/I_n) and T = T_LR(U/U_n)², taken here as constant during the run-up (an approximation; torque actually varies with speed). Start time = Jω/(T_m − T_L). Keep at least 10–20 % accelerating margin and check starts per hour against the starter's thermal rating.

Motor voltage at the current limit53.846%
Motor torque at the limit456.08N·m
Accelerating torque205.83N·m
Start time18.825s
Lowest current limit that starts the load2.5926

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 110 kW pump motor at 3.5 x. The inputs, in the units selected above:

InputValue
Motor rated torque715.00 N·m
Locked-rotor current ratio6.5000 -
Locked-rotor torque ratio2.2000 -
Current limit setting3.5000 -
Average load torque during start35.000 %
Total moment of inertia25.000 kg·m²
Full speed1,480.0 rpm

Applying the formula below gives:

ResultValue
Motor voltage at the current limit53.846 %
Motor torque at the limit456.08 N·m
Accelerating torque205.83 N·m
Start time18.825 s
Lowest current limit that starts the load2.5926

Open this example in the calculator and change any input.

Formula

\(\frac{U}{U_n} = \frac{k}{I_{LR}/I_n}, \quad T_m = T_{LR}\left(\frac U{U_n}\right)^2, \quad t_{st} = \frac{J\omega}{T_m - T_L}\)

Variables

Symbol Meaning SI unit
\(T_n\) Motor rated torque N·m
\(I_{LR}/I_n\) Locked-rotor current ratio -
\(T_{LR}/T_n\) Locked-rotor torque ratio -
\(I_{lim}/I_n\) Current limit setting -
\(T_L/T_n\) Average load torque during start -
\(J\) Total moment of inertia kg·m²
\(n\) Full speed rad/s
\(U/U_n\) Motor voltage at the current limit -
\(T_m\) Motor torque at the limit N·m
\(T_a\) Accelerating torque N·m
\(t_{st}\) Start time s
\((I_{lim}/I_n)_{min}\) Lowest current limit that starts the load -

Method and standards

Soft starting.

Where it is used

  • Setting soft starters for pumps and fans.
  • Checking whether a load can be soft-started.

Common mistakes

  • Expecting full torque at reduced current.
  • Ignoring starts-per-hour limits.

Assumptions and limits

  • Constant motor torque during run-up; average load torque.

References

  • Reduced-voltage torque scaling (T ∝ U², I ∝ U)

Questions and answers

Can a soft starter start any load?

No: torque falls with the square of voltage, so heavy loads like crushers or loaded conveyors may need a VFD.

Why does a lower current limit lengthen the start?

Torque falls with the square of current, leaving less accelerating torque.

What do the defaults represent?

An illustrative 110 kW, 1,480 rpm motor (715 N·m) with 6.5× locked-rotor current and 2.2× torque, a 3.5× current limit, a 35 % load and 25 kg·m² inertia.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Hughes and Drury, Electric Motors and Drives, 5th ed. (Newnes, 2019), Chapman, Electric Machinery Fundamentals, 5th ed. (McGraw-Hill, 2012)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.