Worked example
Example: Illustrative 250 V motor, 200-350 A. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Supply voltage | 250.00 V |
| Armature circuit resistance | 0.40000 Ω |
| Maximum starting current | 350.00 A |
| Current at which a step is cut out | 200.00 A |
Applying the formula below gives:
| Result | Value |
|---|---|
| Total circuit resistance at standstill | 0.71429 Ω |
| Ratio I_min/I_max | 0.57143 |
| Number of resistor steps | 2.0000 |
| Resistance cut out at the first step | 0.30612 Ω |
| Resistance cut out at the last step | 0.008163 Ω |
| Current peak when the last step is shorted | 204.08 A |
Open this example in the calculator and change any input.
Formula
\(R_{tot} = \frac{V_T}{I_{max}}, \quad R_{j+1} = R_j\frac{I_{min}}{I_{max}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V_T\) | Supply voltage | V |
| \(R_A\) | Armature circuit resistance | Ω |
| \(I_{max}\) | Maximum starting current | A |
| \(I_{min}\) | Current at which a step is cut out | A |
| \(R_{tot}\) | Total circuit resistance at standstill | Ω |
| \(k\) | Ratio I_min/I_max | - |
| \(n\) | Number of resistor steps | - |
| \(\Delta R_1\) | Resistance cut out at the first step | Ω |
| \(\Delta R_n\) | Resistance cut out at the last step | Ω |
| \(I_{peak,n}\) | Current peak when the last step is shorted | A |
Method and standards
Starter steps.
Where it is used
- DC motor starter and hoist controller design.
- Teaching DC motor starting.
Common mistakes
- Too few steps giving large current peaks.
- Forgetting the armature resistance is part of the total.
Assumptions and limits
- Steps cut at the same current; inductance and brush drop neglected.
References
- Geometric grading of starter resistance
Questions and answers
Why does a DC motor need a starter?
At standstill there is no back EMF, so the armature current would be V/R_A, many times rated.
Why are the steps geometric?
Each step is cut out at the same current and restores the same maximum, giving equal current ratios.
What do the defaults represent?
An illustrative 250 V motor with 0.4 Ω armature circuit, current kept between 200 and 350 A.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources