Synchronous Motor Excitation for a Power Factor

Armature current, internal EMF, torque angle and field current of a synchronous motor for a power and power factor, from synchronous reactance and the OCC slope.

Inputs

Examples: Illustrative 480 V motor, 0.8 leadingSame motor at unity6.6 kV compressor motor, 0.9 lagging

Accepted: 100 to 15,000 V
Accepted: 0.1 to 100,000 kW
Accepted: 10 to 100 %
Accepted: -1 to 1
Accepted: 0.01 to 1,000 Ω
Accepted: 0 to 100 Ω
Accepted: 10 to 15,000 V
Accepted: 0.1 to 5,000 A

Results

Motor convention: V_φ = E_A + (R_A + jX_s)I_A, so E_A = V_φ − (R_A + jX_s)I_A with I_A at +φ for leading. Over-excited motors (E_A larger) draw leading current and supply reactive power, which is why synchronous motors are used to correct plant power factor. Field current from a linear (unsaturated) open-circuit characteristic I_F = I_F0·E_A/E_0; with saturation more field is needed. δ is the angle by which E_A lags V_φ.

Armature current194.39A
Internal EMF per phase3,822.6V
Torque angle54.583°
Field current needed120.40A
Reactive power (+ supplied to the system)-968.64kvar

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 480 V motor, 0.8 leading. The inputs, in the units selected above:

InputValue
Line voltage (star)480.00 V
Input power80.000 kW
Power factor80.000 %
Leading (+1) or lagging (−1)1.0000 -
Synchronous reactance per phase2.5000 Ω
Armature resistance per phase0 Ω
Phase EMF on the OCC277.00 V
Field current for that EMF4.0000 A

Applying the formula below gives:

ResultValue
Armature current120.28 A
Internal EMF per phase516.94 V
Torque angle27.734 °
Field current needed7.4648 A
Reactive power (+ supplied to the system)60.000 kvar

Open this example in the calculator and change any input.

Formula

\(E_A = V_\phi - (R_A + jX_s)I_A, \quad I_F = I_{F0}\frac{E_A}{E_0}\)

Variables

Symbol Meaning SI unit
\(V_L\) Line voltage (star) V
\(P\) Input power W
\(\cos\varphi\) Power factor -
\(\pm\) Leading (+1) or lagging (−1) -
\(X_s\) Synchronous reactance per phase Ω
\(R_A\) Armature resistance per phase Ω
\(E_0\) Phase EMF on the OCC V
\(I_{F0}\) Field current for that EMF A
\(I_A\) Armature current A
\(E_A\) Internal EMF per phase V
\(\delta\) Torque angle rad
\(I_F\) Field current needed A
\(Q\) Reactive power (+ supplied to the system) var

Method and standards

Excitation.

Where it is used

  • Power factor correction with synchronous motors.
  • Checking field current requirement.

Common mistakes

  • Mixing generator and motor sign conventions.
  • Using line voltage in per-phase phasors.

Assumptions and limits

  • Round rotor; unsaturated OCC; star connection.

References

  • Synchronous machine phasor equations

Questions and answers

How does excitation change the power factor?

At fixed load, raising field current raises E_A, swinging the armature current from lagging through unity to leading.

What is the V-curve?

The plot of armature current against field current at constant load: minimum current at unity power factor.

What do the defaults represent?

An illustrative 480 V star motor taking 80 kW at 0.8 leading, X_s 2.5 Ω, with 277 V per phase at 4 A field.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Chapman, Electric Machinery Fundamentals, 5th ed. (McGraw-Hill, 2012)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.