Worked example
Example: Illustrative 37 kW motor. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Line voltage | 415.00 V |
| No-load current | 18.000 A |
| Share of no-load magnetising kvar | 90.000 % |
| Motor rating | 37.000 kW |
Applying the formula below gives:
| Result | Value |
|---|---|
| No-load reactive power | 12.938 kvar |
| Capacitor rating | 11.645 kvar |
| Capacitor as share of motor kW | 31.472 % |
Open this example in the calculator and change any input.
Formula
\(Q_0 = \sqrt3\,V I_0, \quad Q_c = k\,Q_0\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V\) | Line voltage | V |
| \(I_0\) | No-load current | A |
| \(k\) | Share of no-load magnetising kvar | - |
| \(P\) | Motor rating | W |
| \(Q_0\) | No-load reactive power | var |
| \(Q_c\) | Capacitor rating | var |
| \(Q_c/P\) | Capacitor as share of motor kW | - |
Method and standards
Motor capacitor.
Where it is used
- Individual compensation of induction motors.
- Energy audits.
Common mistakes
- Sizing from full-load power factor.
- Fitting capacitors on star-delta or reversing starters without care.
Assumptions and limits
- No-load current mostly magnetising.
References
- Capacitor limit at 90 % of no-load magnetising kvar
Questions and answers
What capacitor suits a 37 kW motor drawing 18 A at no load on 415 V?
About 11.6 kvar (0.9 × 12.9 kvar).
Why not correct to unity at the motor?
A capacitor above the magnetising kvar can self-excite the motor after switch-off.
What do the defaults represent?
An illustrative 37 kW, 415 V motor with 18 A no-load current, capacitor at 90 % of the no-load kvar.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.