Capacitor Size at Motor Terminals from No-Load Current

Largest capacitor that can be connected directly at an induction motor's terminals without self-excitation, from its no-load current, and the share of motor rating.

Inputs

Examples: Illustrative 37 kW motor7.5 kW motorHT 315 kW motor

Accepted: 100 to 15,000 V
Accepted: 0.1 to 2,000 A
Accepted: 50 to 100 %
Accepted: 0.1 to 10,000 kW

Results

A capacitor switched with the motor corrects its power factor where the reactive current is drawn. If it supplies more than the motor's magnetising kvar, the motor can self-excite after switch-off, generating overvoltage while it runs down and endangering the motor and capacitor; restarting (reversing, star-delta transition) can also be damaging. So the rating is kept to about 90 % of the no-load reactive power, √3·V·I₀. Larger correction goes on the bus with its own switching.

No-load reactive power3.9534kvar
Capacitor rating3.5581kvar
Capacitor as share of motor kW47.441%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 37 kW motor. The inputs, in the units selected above:

InputValue
Line voltage415.00 V
No-load current18.000 A
Share of no-load magnetising kvar90.000 %
Motor rating37.000 kW

Applying the formula below gives:

ResultValue
No-load reactive power12.938 kvar
Capacitor rating11.645 kvar
Capacitor as share of motor kW31.472 %

Open this example in the calculator and change any input.

Formula

\(Q_0 = \sqrt3\,V I_0, \quad Q_c = k\,Q_0\)

Variables

Symbol Meaning SI unit
\(V\) Line voltage V
\(I_0\) No-load current A
\(k\) Share of no-load magnetising kvar -
\(P\) Motor rating W
\(Q_0\) No-load reactive power var
\(Q_c\) Capacitor rating var
\(Q_c/P\) Capacitor as share of motor kW -

Method and standards

Motor capacitor.

Where it is used

  • Individual compensation of induction motors.
  • Energy audits.

Common mistakes

  • Sizing from full-load power factor.
  • Fitting capacitors on star-delta or reversing starters without care.

Assumptions and limits

  • No-load current mostly magnetising.

References

  • Capacitor limit at 90 % of no-load magnetising kvar

Questions and answers

What capacitor suits a 37 kW motor drawing 18 A at no load on 415 V?

About 11.6 kvar (0.9 × 12.9 kvar).

Why not correct to unity at the motor?

A capacitor above the magnetising kvar can self-excite the motor after switch-off.

What do the defaults represent?

An illustrative 37 kW, 415 V motor with 18 A no-load current, capacitor at 90 % of the no-load kvar.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.