Worked example
Example: 3 bar(a), 10 % air. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Total pressure (absolute) | 3.0000 bar |
| Air by volume (mole fraction) in the steam | 10.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Steam partial pressure | 2.7000 bar |
| Saturation temperature of pure steam | 133.53 °C |
| Temperature of the steam–air mixture | 129.97 °C |
| Temperature drop | 3.5575 K |
Open this example in the calculator and change any input.
Formula
\(p_s = p(1 - y_a), \quad T = T_{sat}(p_s), \quad \Delta T = T_{sat}(p) - T\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(p\) | Total pressure (absolute) | Pa |
| \(y_a\) | Air by volume in the steam | - |
| \(p_s\) | Steam partial pressure | Pa |
| \(T_{sat}(p)\) | Saturation temperature of pure steam | K |
| \(T\) | Temperature of the steam–air mixture | K |
| \(\Delta T\) | Temperature drop | K |
Method and standards
Dalton's law.
Where it is used
- Steam system troubleshooting.
- Air vent justification.
Common mistakes
- Air share by mass used as by volume.
Assumptions and limits
- Saturated, well-mixed steam–air mixture: the result is for the bulk composition. Near a condensing surface air accumulates, so the local air share and temperature drop can be much larger.
- The air share is by volume (mole fraction); a mass share entered by mistake understates the drop.
References
- Dalton's law of partial pressures; saturation temperature from IAPWS-IF97
Questions and answers
Why does air lower the temperature?
The gauge reads total pressure, but steam condenses at its own partial pressure.
How much?
Try 10 % air at 3 bar(a): the mixture is several degrees colder than pure steam.
Cure?
Air vents at the far ends of mains and on heat exchangers, especially at start-up.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.