Worked example
Example: Dry air (with argon). The inputs, in the units selected above:
| Input | Value |
|---|---|
| Oxygen (O2) by volume | 20.950 % |
| Nitrogen (N2) by volume | 78.080 % |
| Carbon dioxide (CO2) by volume | 0.040000 % |
| Water vapour (H2O) by volume | 0 % |
| Sulphur dioxide (SO2) by volume | 0 % |
| Carbon monoxide (CO) by volume | 0 % |
| Hydrogen (H2) by volume | 0 % |
| Argon (Ar) by volume | 0.93000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Oxygen by mass | 23.143 % |
| Nitrogen by mass | 75.514 % |
| Carbon dioxide by mass | 0.060773 % |
| Water vapour by mass | 0 % |
| Sulphur dioxide by mass | 0 % |
| Carbon monoxide by mass | 0 % |
| Hydrogen by mass | 0 % |
| Argon by mass | 1.2826 % |
| Mixture molar mass | 28.966 kg/kmol |
Open this example in the calculator and change any input.
Formula
\(M = \sum_i y_i M_i \qquad w_i = \frac{y_i\,M_i}{M}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(y_i\) | mole (volume) fraction of species i: \(y_{O_2}\), \(y_{N_2}\), \(y_{CO_2}\), \(y_{H_2O}\), \(y_{SO_2}\), \(y_{CO}\), \(y_{H_2}\), \(y_{Ar}\) | – |
| \(M_i\) | molar mass of species i | kg/kmol |
| \(M\) | molar mass of the mixture | kg/kmol |
| \(w_i\) | mass fraction of species i: \(w_{O_2}\), \(w_{N_2}\), \(w_{CO_2}\), \(w_{H_2O}\), \(w_{SO_2}\), \(w_{CO}\), \(w_{H_2}\), \(w_{Ar}\) | – |
Method and standards
Molar masses are computed from the IUPAC 2013 conventional atomic weights (C 12.011, H 1.008, O 15.999, N 14.007, S 32.06, Ar 39.948 kg/kmol). The conversion is exact for ideal-gas mixtures.
Where it is used
- Converting gas volumes to mass for balances.
- Emission and fuel calculations.
- Reading supplier data in volume units.
Common mistakes
- Mixing normal and standard conditions.
- Using actual volume with normal density.
- Using the wrong molar mass for a mixture.
Assumptions and limits
- Ideal gas: volume fraction equals mole fraction.
- Only O₂, N₂, CO₂, H₂O, SO₂, CO, H₂ and Ar can be entered; hydrocarbons and H₂S of a fuel gas are not covered.
- Fractions that do not sum to 1 are normalised; the page reports the original sum.
References
- IUPAC 2013 standard atomic weights
Questions and answers
Are volume percent and mole percent the same?
For an ideal gas, yes (Avogadro's law). Flue gas at atmospheric pressure is close enough to ideal for ordinary analysis work.
My analysis does not add up to 100 %. What happens?
The calculator normalises the fractions to 100 % and tells you by how much they were off. Check for a missing component such as water vapour or nitrogen.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.