FireCADCalc

Gas Burner Pressure on a Change of Fuel Gas

New burner supply pressure for the same heat input when the fuel gas changes (heating value and specific gravity), by Ganapathy's flow-resistance relation Δp ∝ W²/ρ.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationChemical and fertiliserPulp and paperFood, dairy and textileFuel oil and gas systemBurner and furnace

Inputs

Examples: Ganapathy: natural gas 4 psig to propaneNatural gas to biogas

Results

Gases of equal Wobbe index give the same heat input at the same pressure; a gas of a different Wobbe index needs new orifices or a different regulator setting, and the air ratio must be reset.

Above about 0.5 bar the gas is compressible and the burner nozzle may choke, so the incompressible Δp ∝ W²/ρ relation is only approximate.

Burner pressure with the new gas60.648kPa
Volume flow ratio, new/old1.6667
Wobbe index ratio0.47683

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Ganapathy: natural gas 4 psig to propane. The inputs, in the units selected above:

InputValue
Burner pressure with the old gas27.579 kPa
Old gas heating value (per standard volume, same reference as the new gas)41.429 MJ/Nm³
Old gas specific gravity (air = 1)0.60000 -
New gas heating value90.750 MJ/Nm³
New gas specific gravity1.5000 -

Applying the formula below gives:

ResultValue
Burner pressure with the new gas14.370 kPa
Volume flow ratio, new/old0.45652
Wobbe index ratio1.3854

Open this example in the calculator and change any input.

Formula

\(\frac{\Delta p_2}{\Delta p_1} = \frac{S_2}{S_1}\left(\frac{HHV_1}{HHV_2}\right)^2, \quad WI = \frac{HHV}{\sqrt{S}}\)

Variables

Symbol Meaning SI unit
\(\Delta p_1\) Burner pressure with the old gas Pa
\(HHV_1\) Old gas heating value (per standard volume) J/m³
\(S_1\) Old gas specific gravity (air = 1) -
\(HHV_2\) New gas heating value J/m³
\(S_2\) New gas specific gravity -
\(\Delta p_2\) Burner pressure with the new gas Pa
\(\dot V_2/\dot V_1\) Volume flow ratio, new/old -
\(WI_2/WI_1\) Wobbe index ratio -

Method and standards

Mass flow = Q/HHV × ρ_std; Δp = K W²/ρ with ρ ∝ S. Only the ratios matter, so both heating values must be on the same basis (both gross, per the same standard volume); the default values are Ganapathy's 1050 and 2300 Btu/scf (60 °F, 14.696 psia) converted to normal m³ at 0 °C.

Where it is used

  • Fuel switching on gas burners.
  • Standby LPG systems.

Common mistakes

  • Ignoring the back pressure in the furnace.
  • Mixing gross and net heating values.

Assumptions and limits

  • Same burner and back pressure; same gas temperature. The burner pressure is the drop across the burner: with a pressurised furnace, or a fixed regulator or valve drop upstream, subtract those from the supply pressure first.
  • Incompressible flow; above about 0.5 bar a note appears.

References

  • Ganapathy
  • Steam Plant Calculations Manual
  • 2nd ed. (Marcel Dekker, 1993)
  • Q2.05
  • Eq. (7): Δp = K W²/ρ

Questions and answers

Why does propane need lower pressure?

It carries more than twice the heat per standard cubic metre, so far less volume flows for the same duty.

What does Ganapathy's example give?

Natural gas at 4 psig switched to propane (2300 Btu/scf, SG 1.5) needs about 2.1 psig.

What does the Wobbe index tell me?

Gases with the same Wobbe index are interchangeable on the same burner.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.