Worked example
Example: Biomass analysis: C 45 %, H 3.5 %, moisture 10 %. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Carbon % | 45.000 % |
| Hydrogen % (excluding moisture) | 3.5000 % |
| Sulphur % | 0.50000 % |
| Nitrogen % | 1.0000 % |
| Oxygen % (excluding moisture) | 5.0000 % |
| Moisture % | 10.000 % |
| Gross calorific value (same basis) | 17,000 kJ/kg |
Applying the formula below gives:
| Result | Value |
|---|---|
| Dry F-factor (dscm per GJ) | 293.22 |
| Wet F-factor (wscm per GJ) | 325.66 |
| Carbon F-factor (scm CO₂ per GJ) | 52.941 |
Open this example in the calculator and change any input.
Formula
\(F_d = K\frac{22.7 H + 9.57 C + 3.54 S + 0.86 N - 2.85 O}{GCV}, \quad F_w = K\frac{34.74 H + 9.57 C + 3.54 S + 0.86 N - 2.85 O + 1.30\,H_2O}{GCV}, \quad F_c = K\frac{2.0 C}{GCV}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(C\) | Carbon % | - |
| \(H\) | Hydrogen % (excluding moisture) | - |
| \(S\) | Sulphur % | - |
| \(N\) | Nitrogen % | - |
| \(O\) | Oxygen % (excluding moisture) | - |
| \(H_2O\) | Moisture % | - |
| \(GCV\) | Gross calorific value (same basis) | J/kg |
| \(F_d\) | Dry F-factor (dscm per GJ) | - |
| \(F_w\) | Wet F-factor (wscm per GJ) | - |
| \(F_c\) | Carbon F-factor (scm CO₂ per GJ) | - |
| \(K\) | 10⁻⁵ (kJ/J)/%, so that with GCV in kJ/kg the F-factor is in m³/J; shown ×10⁹ per GJ | - |
Method and standards
US EPA Method 19 (40 CFR Part 60 Appendix A-7), Eqs. 19-13 to 19-15 in metric form, at 20 °C and 760 mm Hg. The outputs are in m³ per GJ in every unit system; for dscf/MMBtu divide by 0.02684.
Where it is used
- Emission reporting in g/GJ.
- Checking CEMS data.
Common mistakes
- Moisture's hydrogen and oxygen counted in H and O.
Assumptions and limits
- Analysis and GCV on the same basis; hydrogen and oxygen exclude the moisture. The calculator cannot check the basis.
- The analysis must total no more than 100 %, contain some carbon or hydrogen, and give positive F-factors.
References
- US EPA 40 CFR Part 60 Appendix A-7
- Method 19
- Eqs. 19-13 to 19-15 (metric constants Khd 22.7, Kc 9.57, Ks 3.54, Kn 0.86, Ko 2.85, Khw 34.74, Kw 1.30, Kcc 2.0; K = 10⁻⁵)
Questions and answers
What is an F-factor?
The volume of flue gas made per unit of heat in the fuel at stoichiometric combustion.
Why is it handy?
With an F-factor, a stack concentration and O₂ give the emission per unit of heat input, without measuring gas flow.
Typical Fd?
EPA Method 19 Table 19-2 lists about 263 dscm/GJ for bituminous coal and about 248 for wood.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.