Worked example
Example: Staggered boiler bank, 50.8 mm tubes, flue gas about 400 °C, 8 m/s. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Tube arrangement | Staggered |
| Tube outer diameter | 50.800 mm |
| Transverse pitch (across the flow) | 100.00 mm |
| Longitudinal pitch (along the flow) | 90.000 mm |
| Gas velocity approaching the bank | 8.0000 m/s |
| Gas density | 0.55000 kg/m³ |
| Gas dynamic viscosity | 3.2000e-05 Pa·s |
| Gas thermal conductivity | 0.050000 W/(m·K) |
| Gas specific heat | 1.1500 kJ/(kg·K) |
| Prandtl number at the tube wall (0 = same as the gas) | 0 - |
| Correction for fewer than 20 rows (1 for 20 or more) | 1.0000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Maximum velocity in the bank | 16.260 m/s |
| Reynolds number at maximum velocity | 14,197 |
| Prandtl number of the gas | 0.73600 |
| Nusselt number | 99.224 |
| Heat transfer coefficient | 97.661 W/(m²·K) |
Open this example in the calculator and change any input.
Formula
\(V_{max} = \frac{S_T}{S_T - D} V \quad \text{or} \quad \frac{S_T}{2(S_D - D)} V\)
\(Re_{D,max} = \frac{\rho V_{max} D}{\mu}, \quad Pr = \frac{c_p \mu}{k}\)
\(Nu_D = C_2\, C\, Re_{D,max}^m Pr^{n} (Pr/Pr_s)^{1/4}, \quad h = Nu_D k / D\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(D\) | tube outer diameter | m |
| \(S_T\) | transverse pitch | m |
| \(S_L\) | longitudinal pitch | m |
| \(S_D\) | diagonal pitch, staggered | m |
| \(V\) | approach velocity | m/s |
| \(\rho\) | gas density | kg/m³ |
| \(\mu\) | gas dynamic viscosity | Pa·s |
| \(k\) | gas thermal conductivity | W/(m·K) |
| \(c_p\) | gas specific heat | J/(kg·K) |
| \(Pr_s\) | Prandtl number at the wall | - |
| \(C_2\) | row correction for fewer than 20 rows | - |
| \(C, m\) | Zukauskas constants for arrangement and Re | - |
| \(n\) | Prandtl exponent: 0.36 (0.37 for the isolated-cylinder range with Pr up to 10) | - |
| \(\text{arr}\) | tube arrangement | - |
| \(V_{max}\) | maximum velocity | m/s |
| \(Re_{D,max}\) | Reynolds number | - |
| \(Pr\) | Prandtl number | - |
| \(Nu_D\) | Nusselt number | - |
| \(h\) | heat transfer coefficient | W/(m²·K) |
Method and standards
The Zukauskas correlation for banks of 20 or more rows, with constants for Re from 10 to 2 000 000 as tabulated by Incropera (Tables 7.5 and 7.6): from 10 to 100, C = 0.80 in-line and 0.90 staggered with m = 0.40; from 100 to 1 000 the bank is approximated as isolated cylinders (C = 0.51, m = 0.5, Pr exponent 0.37 up to Pr 10); from 1 000, in-line C = 0.27, m = 0.63 up to Re 2×10⁵; staggered C = 0.35 (S_T/S_L)^0.2 (or 0.40 when S_T/S_L ≥ 2), m = 0.60; above 2×10⁵ C = 0.021 or 0.022, m = 0.84. The maximum velocity is at the narrowest gap, transverse or diagonal.
Where it is used
- Rating economisers, air heaters and boiler banks.
- Checking the effect of a velocity or pitch change.
- Estimating U for heat recovery equipment.
Common mistakes
- Using approach velocity instead of maximum velocity in Re.
- Taking gas properties at the inlet instead of the mean temperature.
- Applying it to finned tubes: fins need their own correlation and efficiency.
Assumptions and limits
- Plain tubes in cross-flow; Re 10 to 2 000 000; Pr 0.7 to 500. Below Re 1 000 the constants are less certain and the page says so.
- Gas radiation not included (add it separately at high temperatures).
- Row correction C₂ from the Zukauskas table for shallow banks.
References
- Zukauskas (1972) tube-bank correlation (Incropera Tables 7.5–7.6)
Questions and answers
What gas-side coefficient does a boiler bank have?
Typically 50–150 W/(m²·K). The staggered 50.8 mm example at 8 m/s approach gives Re about 14 200 and h about 98 W/(m²·K).
Why staggered rather than in-line?
Staggered tubes break up the flow more and give a higher coefficient at the same velocity, at a higher pressure drop and with harder cleaning.
What gas properties should I use?
At the mean gas temperature in the bank; take them from the gas properties calculator for the flue gas composition.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.