FireCADCalc

Water and Steam Heat Transfer Coefficient in Tubes

Inside heat transfer coefficient of water or superheated steam flowing in a tube by the Gnielinski and Dittus–Boelter correlations, with IAPWS properties.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliserIAPWS-IF97 (water and steam)BoilerEconomiser and air preheater

Inputs

Examples: Superheater tube: 0.8 kg/s steam, 38 mm ID, 66 bar(a), 450 °CEconomiser tube: 1.2 kg/s water, 38 mm ID, 70 bar(a), 200 °CLow-pressure superheater: 0.25 kg/s, 44 mm, 12 bar(a), 300 °C

Results

Heat transfer coefficient, Gnielinski2,549.0W/(m²·K)
Heat transfer coefficient, Dittus–Boelter2,559.5W/(m²·K)
Reynolds number1,006,443
Prandtl number0.98306
Velocity33.219m/s

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Superheater tube: 0.8 kg/s steam, 38 mm ID, 66 bar(a), 450 °C. The inputs, in the units selected above:

InputValue
Flow through one tube2,880.0 kg/h
Tube inside diameter38.000 mm
Pressure (absolute)66.000 bar
Bulk temperature (single phase: water or superheated steam)450.00 °C

Applying the formula below gives:

ResultValue
Heat transfer coefficient, Gnielinski2,549.0 W/(m²·K)
Heat transfer coefficient, Dittus–Boelter2,559.5 W/(m²·K)
Reynolds number1,006,443
Prandtl number0.98306
Velocity33.219 m/s

Open this example in the calculator and change any input.

Formula

\(Re = \frac{\dot m\,d_i}{A\,\mu} \qquad f = (0.79\ln Re - 1.64)^{-2} \qquad Nu_G = \frac{(f/8)(Re - 1000)\,Pr}{1 + 12.7\sqrt{f/8}\,(Pr^{2/3} - 1)} \qquad h_G = \frac{Nu_G\,k}{d_i}\)

\(h_{DB} = 0.023\,Re^{0.8}\,Pr^{0.4}\,\frac{k}{d_i} \qquad v = \frac{\dot m}{\rho A}\)

Variables

Symbol Meaning SI unit
\(\dot m\) flow through one tube kg/s
\(d_i\) tube inside diameter m
\(p\) pressure, absolute Pa
\(T\) bulk temperature K
\(h_G\) coefficient by Gnielinski W/(m²·K)
\(h_{DB}\) coefficient by Dittus–Boelter W/(m²·K)
\(Re\) Reynolds number –
\(Pr\) Prandtl number –
\(v\) velocity m/s
\(f\) Darcy friction factor (Petukhov) –
\(Nu_G\) Nusselt number –
\(\mu\) dynamic viscosity Pa·s
\(k\) thermal conductivity W/(m·K)
\(\rho\) density kg/m³
\(A\) flow area m²

Method and standards

Gnielinski's correlation with Petukhov's smooth-tube friction factor, and Dittus–Boelter for comparison; properties from FireCAD's IAPWS-IF97 with IAPWS 2008 viscosity and 2011 conductivity at the bulk temperature. The conductivity omits the 2011 release's critical-enhancement term, as its industrial use allows; this makes h about 0.1–0.2 % low for hot water and medium-pressure steam, more near the critical point.

Where it is used

  • Superheater and economiser design.
  • Tube metal temperature checks.
  • Overall coefficient calculations.

Common mistakes

  • Using these correlations in boiling or laminar flow.
  • Taking properties at the wall instead of the bulk temperature.
  • Using the total flow instead of the flow per tube.

Assumptions and limits

  • Fully developed turbulent single-phase flow in smooth tubes; no entrance effect or property-variation correction.
  • Dittus–Boelter is evaluated with Pr^0.4, the exponent for a fluid being heated; for a fluid being cooled the exponent is 0.3. It is shown for comparison only; use the Gnielinski value.

References

  • V. Gnielinski (1976) with Petukhov friction factor
  • Dittus–Boelter (1930)
  • IAPWS R7-97 IF97
  • IAPWS 2008 viscosity
  • IAPWS 2011 conductivity

Questions and answers

What is the steam-side coefficient in a superheater tube?

For 0.8 kg/s of steam at 66 bar(a) and 450 °C in a 38 mm bore, Re is 1.0 million and Gnielinski gives 2550 W/(m²·K); Dittus–Boelter gives 2561.

Gnielinski or Dittus–Boelter?

Gnielinski is more accurate, especially from Re 3000 to 10 000; the two agree in fully turbulent flow.

Can I use it for boiling?

No. Boiling tubes need a boiling correlation; this page refuses two-phase states.

Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.