Worked example
Example: Steam main DN150 (168.3 mm), 180 °C, 75 mm mineral wool 0.045, aluminium cladding. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Pipe outer diameter | 168.30 mm |
| Insulation thickness (0 = bare pipe) | 75.000 mm |
| Insulation thermal conductivity at its mean temperature | 0.045000 W/(m·K) |
| Medium (pipe) temperature | 180.00 °C |
| Ambient air temperature | 25.000 °C |
| Emissivity of the outer surface | 0.10000 - |
| Emissivity of the bare pipe (for comparison) | 0.90000 - |
| Pipe length | 100.00 m |
Applying the formula below gives:
| Result | Value |
|---|---|
| Heat loss per metre | 61.841 W/m |
| Heat loss of the length | 6.1841 kW |
| Outer surface temperature | 40.622 °C |
| Bare pipe heat loss per metre | 1,488.9 W/m |
| Heat loss saved by the insulation | 95.846 % |
| Outer surface coefficient | 3.9586 W/(m²·K) |
| Convection part | 3.3086 W/(m²·K) |
| Radiation part | 0.65006 W/(m²·K) |
| Outer diameter of the insulation | 318.30 mm |
Open this example in the calculator and change any input.
Formula
Conduction through the insulation equals the loss from its outer surface:
\(q' = \frac{2\pi\lambda\,(T_i - T_s)}{\ln(D/D_o)} = h_{se}\,\pi D\,(T_s - T_a) \qquad D = D_o + 2t \qquad Q = q'\,L\)
\(h_{se} = h_{cv} + h_r \qquad h_r = \varepsilon\,\sigma\,\frac{T_s^4 - T_a^4}{T_s - T_a}\)
Natural convection on a horizontal cylinder (ISO 12241), with \(\Delta T = T_s - T_a\):
\(h_{cv} = 1.25\left(\frac{\Delta T}{D}\right)^{1/4}\ \ (D^3\Delta T \le 10\ \text{m}^3\text{K}) \qquad h_{cv} = 1.21\,\Delta T^{1/3}\ \ (D^3\Delta T > 10\ \text{m}^3\text{K})\)
The surface temperature \(T_s\) is solved so that both sides are equal. The bare pipe uses the same surface equations at \(D_o\) and \(T_s = T_i\), with \(\varepsilon_b\), giving \(q'_b\); the saving is \(s = 1 - q'/q'_b\).
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(D_o\) | pipe outer diameter | m |
| \(t\) | insulation thickness | m |
| \(\lambda\) | insulation conductivity at its mean temperature | W/(m·K) |
| \(T_i\) | medium (pipe) temperature | K |
| \(T_a\) | ambient air temperature | K |
| \(\varepsilon\) | emissivity of the outer surface | – |
| \(\varepsilon_b\) | emissivity of the bare pipe | – |
| \(L\) | pipe length | m |
| \(q'\) | heat loss per metre | W/m |
| \(Q\) | heat loss of the length | W |
| \(T_s\) | outer surface temperature | K |
| \(q'_b\) | bare pipe heat loss per metre | W/m |
| \(s\) | share of the bare loss saved | – |
| \(h_{se}\) | outer surface coefficient | W/(m²·K) |
| \(h_{cv}\) | convection coefficient | W/(m²·K) |
| \(h_r\) | radiation coefficient | W/(m²·K) |
| \(D\) | outer diameter of the insulation | m |
| \(\sigma\) | Stefan–Boltzmann constant, 5.670 374 419 × 10⁻⁸ | W/(m²·K⁴) |
Method and standards
ISO 12241:2008 (thermal insulation for building equipment and industrial installations): steady conduction through a cylindrical layer, and an outer surface coefficient made of the standard's natural-convection equations for horizontal pipes in still air plus linearised radiation to surroundings at the air temperature. The surface temperature is found by a bracketed root solver. Stefan–Boltzmann constant from CODATA 2018.
Where it is used
- Insulation thickness selection for steam and hot water lines.
- Energy audits of bare and damaged insulation.
- Personnel protection surface temperature checks.
Common mistakes
- Using the conductivity at room temperature for hot insulation.
- Ignoring wind on outdoor lines.
- Using the emissivity of new cladding for weathered surfaces.
Assumptions and limits
- Horizontal pipe, still indoor air, surroundings at the air temperature. Wind outdoors raises h_se and lowers the surface temperature; the heat loss changes little for well-insulated pipes.
- Inner film and pipe wall resistances neglected: the inner insulation surface is at the medium temperature.
- One insulation layer with a constant conductivity; for two layers, or a conductivity that varies strongly with temperature, the result is approximate.
- No allowance for supports, flanges, valves or damaged insulation; add them as equivalent lengths.
References
- ISO 12241:2008 (horizontal pipes, still air)
- CODATA 2018 (Stefan–Boltzmann constant)
Questions and answers
How much heat does an insulated steam pipe lose?
A DN150 steam main at 180 °C with 75 mm of mineral wool (0.045 W/(m·K)) and aluminium cladding in 25 °C still air loses 61.8 W per metre. Bare, it would lose 1 489 W/m.
Why is the cladding hotter with aluminium than with paint?
Bright aluminium has an emissivity of about 0.1, so it radiates little heat. The surface must run hotter to lose the same heat by convection: 40.6 °C in the example, where a painted surface would be cooler.
Which conductivity should I enter?
The insulation's conductivity at its mean temperature, from the maker's data. Conductivity rises with temperature, so a value at 20 °C understates the loss of a hot pipe.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.