Worked example
Example: Bare 4-inch pipe at 150 °C in 20 °C air. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Fluid | Air (dry) |
| Surface temperature | 150.00 °C |
| Fluid temperature | 20.000 °C |
| Outside diameter | 114.30 mm |
| Pressure (absolute) | 1.0132 bar |
Applying the formula below gives:
| Result | Value |
|---|---|
| Rayleigh number | 8,562,243 |
| Nusselt number | 27.133 |
| Convection coefficient | 6.8481 W/(m²·K) |
| Heat loss per metre | 319.68 W/m |
Open this example in the calculator and change any input.
Formula
\(Ra_D = \frac{g\beta\,|T_s - T_\infty|\,D^3}{\nu\alpha}, \quad \overline{Nu}_D = \left\{0.60 + \frac{0.387 Ra_D^{1/6}}{\left[1 + (0.559/Pr)^{9/16}\right]^{8/27}}\right\}^2, \quad h = \frac{Nu\,k}{D}, \quad q' = h\pi D(T_s - T_\infty)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\text{fluid}\) | Fluid | - |
| \(T_s\) | Surface temperature | K |
| \(T_\infty\) | Fluid temperature | K |
| \(D\) | Outside diameter | m |
| \(p\) | Pressure (absolute) | Pa |
| \(Ra\) | Rayleigh number | - |
| \(Nu\) | Nusselt number | - |
| \(h\) | Convection coefficient | W/(m²·K) |
| \(q'\) | Heat loss per metre | W/m |
Method and standards
Churchill–Chu for horizontal cylinders.
Where it is used
- Bare and insulated pipe losses.
- Heat tracing.
Common mistakes
- Forgetting radiation.
- Using it for vertical pipes.
Assumptions and limits
- Isothermal cylinder in still fluid; properties at the film temperature (T_s + T_∞)/2. β = 1/T for air (ideal gas); for water β from the IF97 density 0.5 K either side of the film temperature.
- Ra up to 10¹² (a note is shown above it). Water at or above its boiling point is rejected (boiling is not covered).
References
- S.W. Churchill and H.H.S. Chu
- Int. J. Heat Mass Transfer 18 (1975) 1049
- Incropera
- DeWitt
- Bergman and Lavine
- Fundamentals of Heat and Mass Transfer
- ch. 9
- Air from NIST Shomate
- Sutherland and Eucken (engine); water from IAPWS-IF97 and the IAPWS 2008/2011 transport releases
Questions and answers
A bare 4-inch pipe at 150 °C in 20 °C air?
About 6.8 W/(m²·K) by convection, roughly 320 W per metre; radiation adds a similar amount.
Why does diameter matter little?
h falls slowly as D grows, while area grows.
What range?
Ra up to 10¹².
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.