LMTD (Log Mean Temperature Difference)

Log mean temperature difference of a heat exchanger in counterflow or parallel flow from the four terminal temperatures, with the F correction factor.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliserThermic fluid heatingBoilerBoiler operation engineer (BOE) examinations

Inputs

Examples: Counterflow: oil 150 to 90 °C, water 30 to 70 °CParallel flow, same temperaturesEconomiser: gas 350 to 180 °C, water 105 to 160 °C, F = 0.97Balanced counterflow, equal differences 40 K

Temperatures

For shell-and-tube exchangers with more than one tube pass, and for cross-flow, read F from the TEMA or textbook charts; 1 for true counterflow or a condensing or boiling stream.

Results

Log mean temperature difference40.000K
Corrected mean temperature difference40.000K
Terminal difference at the hot inlet end40.000K
Terminal difference at the hot outlet end40.000K

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Counterflow: oil 150 to 90 °C, water 30 to 70 °C. The inputs, in the units selected above:

InputValue
Hot stream inlet150.00 °C
Hot stream outlet90.000 °C
Cold stream inlet30.000 °C
Cold stream outlet70.000 °C
Flow arrangementCounterflow
LMTD correction factor (1 for pure counterflow)1.0000 -

Applying the formula below gives:

ResultValue
Log mean temperature difference69.521 K
Corrected mean temperature difference69.521 K
Terminal difference at the hot inlet end80.000 K
Terminal difference at the hot outlet end60.000 K

Open this example in the calculator and change any input.

Formula

Counterflow: \(\Delta T_1 = T_{h,in} - T_{c,out}\), \(\Delta T_2 = T_{h,out} - T_{c,in}\). Parallel flow: \(\Delta T_1 = T_{h,in} - T_{c,in}\), \(\Delta T_2 = T_{h,out} - T_{c,out}\).

\(\Delta T_{lm} = \frac{\Delta T_1 - \Delta T_2}{\ln(\Delta T_1/\Delta T_2)} \qquad \text{corrected: } F\,\Delta T_{lm}\)

Variables

Symbol Meaning SI unit
\(T_{h,in}\) hot stream inlet temperature K
\(T_{h,out}\) hot stream outlet temperature K
\(T_{c,in}\) cold stream inlet temperature K
\(T_{c,out}\) cold stream outlet temperature K
\(\text{flow}\) counterflow or parallel flow –
\(F\) LMTD correction factor –
\(\Delta T_{lm}\) log mean temperature difference K
\(F\,\Delta T_{lm}\) corrected mean temperature difference K
\(\Delta T_1\) terminal difference at the hot inlet end K
\(\Delta T_2\) terminal difference at the hot outlet end K

Method and standards

The log mean temperature difference for counterflow and parallel-flow exchangers with constant specific heats and overall coefficient (Incropera, Fundamentals of Heat and Mass Transfer, ch. 11). Other arrangements use the counterflow LMTD times the correction factor F read from the charts for the exchanger type (TEMA, textbooks).

Where it is used

  • Heat exchanger design and rating.
  • Condensers, economisers, air heaters and process coolers.
  • Back-calculating U from plant readings.

Common mistakes

  • Using the arithmetic mean difference when the ends differ a lot.
  • Forgetting the correction factor F for multipass exchangers.
  • Mixing up which ends pair in counterflow.

Assumptions and limits

  • Constant specific heats and overall coefficient along the exchanger; no phase change with a change of temperature.
  • When ΔT₁ = ΔT₂ the LMTD equals that difference.
  • A temperature cross (a terminal difference of zero or less) is rejected for the arrangement chosen.
  • F applies to the counterflow LMTD; F below 1 with parallel flow is flagged.

References

  • Incropera
  • Fundamentals of Heat and Mass Transfer
  • ch. 11; TEMA (F factor charts)

Questions and answers

How do I calculate LMTD?

LMTD = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂). Oil from 150 to 90 °C against water from 30 to 70 °C in counterflow gives ΔT₁ = 80 K, ΔT₂ = 60 K and an LMTD of 69.5 K.

Why is counterflow better than parallel flow?

With the same four temperatures the parallel-flow LMTD in that example is only 55.8 K, so the exchanger needs 25 % more area. Counterflow also lets the cold stream leave hotter than the hot stream's outlet.

What is the F factor?

Multi-pass shell-and-tube and cross-flow exchangers are not pure counterflow. Their mean temperature difference is F × the counterflow LMTD, with F from charts for the exchanger type; F = 1 when one stream condenses or boils at constant temperature.

Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.