FireCADCalc

Effect of Fouling on a Heat Exchanger (Clean vs Dirty U)

Dirty overall coefficient from the clean coefficient and the fouling resistances, the extra area needed, and the duty lost by an existing exchanger at the same LMTD.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: Clean 850, cooling water 0.00018, process 0.00035Condenser clean 3 000, 0.0001 and 0Gas cooler clean 60, 0.0002 and 0.0004

Results

Fouling resistances from your experience or a published table (TEMA). Lower LMTD after fouling also lowers duty further in practice.

Dirty (service) coefficient586.00W/(m²·K)
Extra area needed for the same duty45.050%
Duty lost at the same LMTD31.058%
Cleanliness factor68.942%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Clean 850, cooling water 0.00018, process 0.00035. The inputs, in the units selected above:

InputValue
Clean overall coefficient850.00 W/(m²·K)
Fouling resistance, inside, referred to the outside area (R_fi d_o/d_i)1.8000e-04 m²·K/W
Fouling resistance, outside (referred to the same area)3.5000e-04 m²·K/W

Applying the formula below gives:

ResultValue
Dirty (service) coefficient586.00 W/(m²·K)
Extra area needed for the same duty45.050 %
Duty lost at the same LMTD31.058 %
Cleanliness factor68.942 %

Open this example in the calculator and change any input.

Formula

\(\frac{1}{U_d} = \frac{1}{U_c} + R_{f,i} + R_{f,o}\)

Variables

Symbol Meaning SI unit
\(U_c\) Clean overall coefficient W/(m²·K)
\(R_{f,i}\) Fouling resistance, inside, referred to the outside area (R_fi d_o/d_i) m²·K/W
\(R_{f,o}\) Fouling resistance, outside (referred to the same area) m²·K/W
\(U_d\) Dirty (service) coefficient W/(m²·K)
\(A_d/A_c - 1\) Extra area needed for the same duty -
\(1 - U_d/U_c\) Duty lost at the same LMTD -
\(U_d/U_c\) Cleanliness factor -

Method and standards

Resistances in series.

Where it is used

  • Exchanger design margins.
  • Cleaning schedules.

Common mistakes

  • Inside fouling not referred to the outside area.
  • Over-generous fouling factors.

Assumptions and limits

  • Uniform fouling.
  • Both resistances on the area basis of U_c (usually the outside area): multiply an inside resistance by d_o/d_i before entering it.

References

  • 1/U_d = 1/U_c + R_f
  • i + R_f
  • o (Kern, Process Heat Transfer)

Questions and answers

Clean U 850 with 0.00053 m²·K/W of fouling?

Dirty U 586 W/(m²·K): 45 % more area needed.

Why does fouling hit high-U exchangers hardest?

The same resistance is a larger share of a small total resistance.

What is a cleanliness factor?

U_dirty/U_clean, used for condensers.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.