FireCADCalc

Heat Exchanger Duty and Outlet Temperature Balance

Heat duty of a heat exchanger from one stream's flow and temperatures, and the other stream's outlet temperature or flow needed, by energy balance.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: 5 kg/s water 80→50 °C heating 8 kg/s from 25 °C; 45 °C wantedOil cooler: 2 kg/s oil 2 100 J/kgK 90→60 °C, 3 kg/s water from 30 °C, 2 % lossAir heater: 10 kg/s air heated 20→80 °C by 1.5 kg/s thermal oil at 250 °C

Results

Duty from stream 1126.00kW
Stream 2 outlet at its flow39.847°C
Stream 2 flow for the outlet wanted10,635kg/h

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 5 kg/s water 80→50 °C heating 8 kg/s from 25 °C; 45 °C wanted. The inputs, in the units selected above:

InputValue
Flow of stream 118,000 kg/h
Specific heat of stream 14.1800 kJ/(kg·K)
Stream 1 inlet80.000 °C
Stream 1 outlet50.000 °C
Flow of stream 228,800 kg/h
Specific heat of stream 24.1800 kJ/(kg·K)
Stream 2 inlet25.000 °C
Stream 2 outlet wanted (for the flow needed)45.000 °C
Heat loss as a share of the duty0 %

Applying the formula below gives:

ResultValue
Duty from stream 1627.00 kW
Stream 2 outlet at its flow43.750 °C
Stream 2 flow for the outlet wanted27,000 kg/h

Open this example in the calculator and change any input.

Formula

\(\dot Q = \dot m_1 c_{p1}(T_{1,in} - T_{1,out}), \quad \dot Q_2 = \dot Q(1 - \epsilon_l)\ (\dot Q \ge 0),\ \ \frac{\dot Q}{1 - \epsilon_l}\ (\dot Q < 0), \quad T_{2,out} = T_{2,in} + \frac{\dot Q_2}{\dot m_2 c_{p2}}, \quad \dot m_{2,req} = \frac{\dot Q_2}{c_{p2}(T_{2,out,w} - T_{2,in})}\)

Variables

Symbol Meaning SI unit
\(\dot m_1\) Flow of stream 1 kg/s
\(c_{p1}\) Specific heat of stream 1 J/(kg·K)
\(T_{1,in}\) Stream 1 inlet K
\(T_{1,out}\) Stream 1 outlet K
\(\dot m_2\) Flow of stream 2 kg/s
\(c_{p2}\) Specific heat of stream 2 J/(kg·K)
\(T_{2,in}\) Stream 2 inlet K
\(T_{2,out,w}\) Stream 2 outlet wanted (for the flow needed) K
\(\epsilon_l\) Heat loss as a share of the duty -
\(\dot Q\) Duty from stream 1 W
\(T_{2,out}\) Stream 2 outlet at its flow K
\(\dot m_{2,req}\) Stream 2 flow for the outlet wanted kg/s

Method and standards

Energy balance.

Where it is used

  • Exchanger checks and cooling water.
  • Process design.

Common mistakes

  • Mixing kg/h and kg/s.
  • c_p ΔT across a phase change.

Assumptions and limits

  • No phase change, constant c_p.
  • The heat loss is taken from the hot side: when stream 1 is hot, stream 2 receives Q(1 − ε_l); when stream 1 is cold, stream 2 must give |Q|/(1 − ε_l).
  • A stream 2 outlet beyond stream 1's inlet (impossible) is flagged.

References

  • Steady-flow energy balance Q = ṁ c_p ΔT

Questions and answers

5 kg/s of water from 80 to 50 °C heats 8 kg/s from 25 °C?

Duty 627 kW; the cold stream leaves at 43.75 °C.

What flow for a 45 °C outlet?

7.5 kg/s.

Phase change?

Use enthalpies (steam tables) instead of c_p ΔT.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.