Worked example
Example: 5 kg/s water 80→50 °C heating 8 kg/s from 25 °C; 45 °C wanted. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Flow of stream 1 | 18,000 kg/h |
| Specific heat of stream 1 | 4.1800 kJ/(kg·K) |
| Stream 1 inlet | 80.000 °C |
| Stream 1 outlet | 50.000 °C |
| Flow of stream 2 | 28,800 kg/h |
| Specific heat of stream 2 | 4.1800 kJ/(kg·K) |
| Stream 2 inlet | 25.000 °C |
| Stream 2 outlet wanted (for the flow needed) | 45.000 °C |
| Heat loss as a share of the duty | 0 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Duty from stream 1 | 627.00 kW |
| Stream 2 outlet at its flow | 43.750 °C |
| Stream 2 flow for the outlet wanted | 27,000 kg/h |
Open this example in the calculator and change any input.
Formula
\(\dot Q = \dot m_1 c_{p1}(T_{1,in} - T_{1,out}), \quad \dot Q_2 = \dot Q(1 - \epsilon_l)\ (\dot Q \ge 0),\ \ \frac{\dot Q}{1 - \epsilon_l}\ (\dot Q < 0), \quad T_{2,out} = T_{2,in} + \frac{\dot Q_2}{\dot m_2 c_{p2}}, \quad \dot m_{2,req} = \frac{\dot Q_2}{c_{p2}(T_{2,out,w} - T_{2,in})}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m_1\) | Flow of stream 1 | kg/s |
| \(c_{p1}\) | Specific heat of stream 1 | J/(kg·K) |
| \(T_{1,in}\) | Stream 1 inlet | K |
| \(T_{1,out}\) | Stream 1 outlet | K |
| \(\dot m_2\) | Flow of stream 2 | kg/s |
| \(c_{p2}\) | Specific heat of stream 2 | J/(kg·K) |
| \(T_{2,in}\) | Stream 2 inlet | K |
| \(T_{2,out,w}\) | Stream 2 outlet wanted (for the flow needed) | K |
| \(\epsilon_l\) | Heat loss as a share of the duty | - |
| \(\dot Q\) | Duty from stream 1 | W |
| \(T_{2,out}\) | Stream 2 outlet at its flow | K |
| \(\dot m_{2,req}\) | Stream 2 flow for the outlet wanted | kg/s |
Method and standards
Energy balance.
Where it is used
- Exchanger checks and cooling water.
- Process design.
Common mistakes
- Mixing kg/h and kg/s.
- c_p ΔT across a phase change.
Assumptions and limits
- No phase change, constant c_p.
- The heat loss is taken from the hot side: when stream 1 is hot, stream 2 receives Q(1 − ε_l); when stream 1 is cold, stream 2 must give |Q|/(1 − ε_l).
- A stream 2 outlet beyond stream 1's inlet (impossible) is flagged.
References
- Steady-flow energy balance Q = ṁ c_p ΔT
Questions and answers
5 kg/s of water from 80 to 50 °C heats 8 kg/s from 25 °C?
Duty 627 kW; the cold stream leaves at 43.75 °C.
What flow for a 45 °C outlet?
7.5 kg/s.
Phase change?
Use enthalpies (steam tables) instead of c_p ΔT.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.