Time-of-Use Tariff: Saving from Shifting Load

Yearly saving from moving energy from peak to off-peak hours under a time-of-use tariff, allowing for storage losses and any demand-charge reduction.

Inputs

Examples: Illustrative 500 kWh shifted with 100 kW demand cutBattery, 88 % round tripIce storage

Accepted: 0 to 277,780 kWh
Accepted: 0 to 1,000
Accepted: 0 to 1,000
Accepted: 30 to 100 %
Accepted: 0 to 1,000,000 kW
Accepted: 0 to 10,000
Accepted: 1 to 366

Results

Each kWh moved out of the peak saves the peak rate but costs the off-peak rate for the energy needed to replace it; with storage (batteries, chilled-water or ice tanks, hot-water tanks) the losses raise that to E/η. Shifting pays only if the round-trip efficiency is above the ratio of off-peak to peak rates. If shifting also lowers the billed maximum demand, the demand charge saving is often larger than the energy saving.

Energy saving per day7,588.2
Energy saving per year1,365,882
Demand charge saving per year0
Total saving per year1,365,882
Break-even efficiency (below this, shifting costs money)61.111%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 500 kWh shifted with 100 kW demand cut. The inputs, in the units selected above:

InputValue
Energy shifted per day (at the load)500.00 kWh
Peak energy rate per kWh11.000 -
Off-peak energy rate per kWh6.0000 -
Round-trip efficiency (1 for moving the process itself)100.00 %
Reduction in billed maximum demand100.00 kW
Demand charge per kW per month350.00 -
Days per year shifted300.00 -

Applying the formula below gives:

ResultValue
Energy saving per day2,500.0
Energy saving per year750,000
Demand charge saving per year420,000
Total saving per year1,170,000
Break-even efficiency (below this, shifting costs money)54.545 %

Open this example in the calculator and change any input.

Formula

\(\Delta C_e = E\,c_p - \frac{E}{\eta}c_o, \quad \Delta C = n\,\Delta C_e + 12\,\Delta P\,c_d\)

Variables

Symbol Meaning SI unit
\(E\) Energy shifted per day (at the load) J
\(c_p\) Peak energy rate per kWh -
\(c_o\) Off-peak energy rate per kWh -
\(\eta\) Round-trip efficiency (1 for moving the process itself) -
\(\Delta P\) Reduction in billed maximum demand W
\(c_d\) Demand charge per kW per month -
\(n\) Days per year shifted -
\(\Delta C_e\) Energy saving per day -
\(\Delta C_{e,y}\) Energy saving per year -
\(\Delta C_{d,y}\) Demand charge saving per year -
\(\Delta C\) Total saving per year -
\(c_o/c_p\) Break-even efficiency (below this, shifting costs money) -

Method and standards

Time-of-use.

Where it is used

  • Scheduling batch processes and pumping.
  • Business case for thermal and battery storage.

Common mistakes

  • Ignoring storage losses.
  • Counting a demand reduction that the billing method does not recognise.

Assumptions and limits

  • Constant tariffs; same energy at the load.

References

  • Time-of-use tariff arithmetic with storage round-trip efficiency

Questions and answers

Does battery storage always pay under a TOD tariff?

Only if its round-trip efficiency exceeds the off-peak to peak price ratio, and the saving covers the battery's cost and wear.

Is the demand charge saving included?

Yes, as kW reduced × monthly rate × 12.

What do the defaults represent?

An illustrative plant moving 500 kWh a day from a peak rate of 11 to an off-peak rate of 6 per kWh, cutting maximum demand by 100 kW.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.