Worked example
Example: Illustrative 500 kWh shifted with 100 kW demand cut. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Energy shifted per day (at the load) | 500.00 kWh |
| Peak energy rate per kWh | 11.000 - |
| Off-peak energy rate per kWh | 6.0000 - |
| Round-trip efficiency (1 for moving the process itself) | 100.00 % |
| Reduction in billed maximum demand | 100.00 kW |
| Demand charge per kW per month | 350.00 - |
| Days per year shifted | 300.00 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Energy saving per day | 2,500.0 |
| Energy saving per year | 750,000 |
| Demand charge saving per year | 420,000 |
| Total saving per year | 1,170,000 |
| Break-even efficiency (below this, shifting costs money) | 54.545 % |
Open this example in the calculator and change any input.
Formula
\(\Delta C_e = E\,c_p - \frac{E}{\eta}c_o, \quad \Delta C = n\,\Delta C_e + 12\,\Delta P\,c_d\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(E\) | Energy shifted per day (at the load) | J |
| \(c_p\) | Peak energy rate per kWh | - |
| \(c_o\) | Off-peak energy rate per kWh | - |
| \(\eta\) | Round-trip efficiency (1 for moving the process itself) | - |
| \(\Delta P\) | Reduction in billed maximum demand | W |
| \(c_d\) | Demand charge per kW per month | - |
| \(n\) | Days per year shifted | - |
| \(\Delta C_e\) | Energy saving per day | - |
| \(\Delta C_{e,y}\) | Energy saving per year | - |
| \(\Delta C_{d,y}\) | Demand charge saving per year | - |
| \(\Delta C\) | Total saving per year | - |
| \(c_o/c_p\) | Break-even efficiency (below this, shifting costs money) | - |
Method and standards
Time-of-use.
Where it is used
- Scheduling batch processes and pumping.
- Business case for thermal and battery storage.
Common mistakes
- Ignoring storage losses.
- Counting a demand reduction that the billing method does not recognise.
Assumptions and limits
- Constant tariffs; same energy at the load.
References
- Time-of-use tariff arithmetic with storage round-trip efficiency
Questions and answers
Does battery storage always pay under a TOD tariff?
Only if its round-trip efficiency exceeds the off-peak to peak price ratio, and the saving covers the battery's cost and wear.
Is the demand charge saving included?
Yes, as kW reduced × monthly rate × 12.
What do the defaults represent?
An illustrative plant moving 500 kWh a day from a peak rate of 11 to an off-peak rate of 6 per kWh, cutting maximum demand by 100 kW.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.