Synchronous Generator Voltage Regulation

Internal EMF, torque angle and percent voltage regulation of a synchronous generator at a load current and power factor angle from its per-phase impedance.

Inputs

Examples: Illustrative 480 V 60 kVA at 0.8 laggingSame at 0.8 leading11 kV 5 MVA at unity

Accepted: 100 to 30,000 V
Accepted: 0.1 to 2,000,000 kVA
Accepted: -90 to 90 °
Accepted: 0 to 100 Ω
Accepted: 0.001 to 1,000 Ω

Results

Generator: E_A = V_φ + (R_A + jX_s)I_A, with I_A at −φ for lagging load. VR = (E_A − V_φ)/V_φ is the rise in terminal voltage if the load is removed at constant field and speed. Lagging loads give large positive regulation; leading loads can give negative regulation (voltage would fall on load rejection). The synchronous-impedance method ignores saturation and overstates regulation at high field.

Armature current72.169A
Internal EMF per phase273.74V
Torque angle1.3445°
Voltage regulation-1.2228%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 480 V 60 kVA at 0.8 lagging. The inputs, in the units selected above:

InputValue
Rated line voltage (star)480.00 V
Load apparent power60.000 kVA
Power factor angle (+ lagging, − leading)36.870 °
Armature resistance per phase0.015000 Ω
Synchronous reactance per phase0.10000 Ω

Applying the formula below gives:

ResultValue
Armature current72.169 A
Internal EMF per phase282.37 V
Torque angle1.0398 °
Voltage regulation1.8918 %

Open this example in the calculator and change any input.

Formula

\(E_A = V_\phi + (R_A + jX_s)I_A, \quad VR = \frac{E_A - V_\phi}{V_\phi}\)

Variables

Symbol Meaning SI unit
\(V_L\) Rated line voltage (star) V
\(S\) Load apparent power VA
\(\varphi\) Power factor angle (+ lagging, − leading) rad
\(R_A\) Armature resistance per phase Ω
\(X_s\) Synchronous reactance per phase Ω
\(I_A\) Armature current A
\(E_A\) Internal EMF per phase V
\(\delta\) Torque angle rad
\(VR\) Voltage regulation -

Method and standards

Regulation.

Where it is used

  • Alternator selection and AVR range checks.
  • Teaching synchronous machine phasors.

Common mistakes

  • Mixing line and phase voltages.
  • Wrong sign of the power factor angle.

Assumptions and limits

  • Round rotor; unsaturated; star connection; balanced load.

References

  • Synchronous impedance (EMF) method

Questions and answers

Why is regulation worse for lagging loads?

Lagging current's reactive drop across X_s directly opposes the terminal voltage, so more EMF is needed.

Can regulation be negative?

Yes, with leading (capacitive) loads the reactive drop adds to the terminal voltage.

What do the defaults represent?

An illustrative 480 V, 60 kVA generator at 0.8 power factor lagging with R_A 0.015 Ω and X_s 0.1 Ω per phase.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Chapman, Electric Machinery Fundamentals, 5th ed. (McGraw-Hill, 2012)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.