Magnetohydrodynamic (MHD) Generator Power Density

Open-circuit field, current density and power density of an MHD generator channel from gas conductivity, velocity, magnetic field and load factor.

Thermal power plant

Inputs

Examples: Illustrative 20 S/m, 800 m/s, 5 T, k 0.75Maximum power k 0.5Low field 3 T, 40 S/m

Accepted: 1,000 to 100,000,000 µS/cm
Accepted: 10 to 3,000 m/s
Accepted: 0.1 to 10 T
Accepted: 0 to 100 %
Accepted: 0.01 to 1,000 m³

Results

Faraday channel with continuous electrodes: J = σuB(1 − k), P/V = σu²B²k(1 − k); the electrical (local) efficiency equals k. Seeded combustion gas reaches about 10–50 S/m at 2,500–3,000 K; Hall effects and electrode losses lower real output.

Open-circuit field uB4,000.0
Current density2.0000A/cm²
Power density60.000MW/m³
Electrical power600.00MW
Power density at k = 0.580.000MW/m³

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 20 S/m, 800 m/s, 5 T, k 0.75. The inputs, in the units selected above:

InputValue
Gas electrical conductivity200,000 µS/cm
Gas velocity800.00 m/s
Magnetic flux density5.0000 T
Load factor (load voltage over open-circuit)75.000 %
Active channel volume10.000 m³

Applying the formula below gives:

ResultValue
Open-circuit field uB4,000.0
Current density2.0000 A/cm²
Power density60.000 MW/m³
Electrical power600.00 MW
Power density at k = 0.580.000 MW/m³

Open this example in the calculator and change any input.

Formula

\(\frac{P}{V} = \sigma u^2B^2k(1 - k), \quad J = \sigma uB(1 - k)\)

Variables

Symbol Meaning SI unit
\(\sigma\) Gas electrical conductivity S/m
\(u\) Gas velocity m/s
\(B\) Magnetic flux density T
\(k\) Load factor (load voltage over open-circuit) -
\(V\) Active channel volume m³
\(E_{oc}\) Open-circuit field uB -
\(J\) Current density A/m²
\(P/V\) Power density W/m³
\(P\) Electrical power W
\((P/V)_{max}\) Power density at k = 0.5 W/m³

Method and standards

MHD generation.

Where it is used

  • Teaching direct energy conversion.
  • Topping-cycle studies.

Common mistakes

  • Using peak power density with efficiency k = 0.5.
  • Ignoring Hall effects.

Assumptions and limits

  • Ideal Faraday generator; uniform properties.

References

  • Ideal Faraday MHD generator

Questions and answers

Why has MHD not been adopted?

It needs gas above 2,500 K seeded with potassium, strong superconducting magnets and electrodes that survive slag and heat; combined cycles proved cheaper.

What is the load factor?

The ratio of load voltage to the open-circuit uB; power density is greatest at 0.5, but efficiency equals the load factor, so 0.7–0.8 is used.

What do the defaults represent?

An illustrative channel: 20 S/m seeded gas at 800 m/s in a 5 T field, load factor 0.75, 10 m³.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Kothari, Singal and Ranjan, Renewable Energy Sources and Emerging Technologies, 2nd ed. (PHI, 2011)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.