FireCADCalc

Long Transmission Line: Exact ABCD Parameters and Performance

Sending-end voltage, current, power factor, efficiency and regulation of a long line from per-km R, L and C by the exact hyperbolic ABCD constants.

Thermal power plant

Inputs

Examples: Illustrative: 400 kV, 350 km, 300 MW at 0.9220 kV, 300 km, 120 MW at 0.85, 60 Hz765 kV, 500 km, 1500 MW at 0.95

Accepted: 1 to 1,500 kV
Accepted: 0.001 to 10,000 MW
Accepted: 10 to 100 %
Accepted: 0 to 1,000 Ω/km
Accepted: 0.01 to 100 mH/km
Accepted: 0.1 to 100,000 nF/km
Accepted: 1 to 5,000 km
Accepted: 1 to 1,000 Hz

Results

Exact distributed-parameter model: A = D = cosh γℓ, B = Z_c sinh γℓ, C = sinh γℓ / Z_c, per phase with balanced load. Shunt conductance is neglected. Regulation uses the receiving voltage at no load, V_S/|A| (Ferranti rise).

Characteristic (surge) impedance260.30Ω
Electrical length |γℓ|0.53154
Magnitude of A = cosh γℓ0.86217
Sending-end line voltage798.51kV
Sending-end current1,118.6A
Sending-end power factor0.98404
Efficiency98.526%
Voltage regulation21.067%
Surge impedance loading2,248.3MW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative: 400 kV, 350 km, 300 MW at 0.9. The inputs, in the units selected above:

InputValue
Receiving-end line voltage400.00 kV
Load power300.00 MW
Load power factor (lagging)90.000 %
Resistance per phase per km0.030000 Ω/km
Inductance per phase per km1.0000 mH/km
Capacitance per phase per km11.500 nF/km
Line length350.00 km
Frequency50.000 Hz

Applying the formula below gives:

ResultValue
Characteristic (surge) impedance295.55 Ω
Electrical length |γℓ|0.37373
Magnitude of A = cosh γℓ0.93130
Sending-end line voltage426.54 kV
Sending-end current414.50 A
Sending-end power factor0.99927
Efficiency98.039 %
Voltage regulation14.500 %
Surge impedance loading541.36 MW

Open this example in the calculator and change any input.

Formula

\(\gamma = \sqrt{zy}, \quad Z_c = \sqrt{z/y}, \quad A = D = \cosh\gamma\ell, \quad B = Z_c\sinh\gamma\ell, \quad C = \frac{\sinh\gamma\ell}{Z_c}\)

\(V_S = AV_R + BI_R, \quad I_S = CV_R + AI_R\)

Variables

Symbol Meaning SI unit
\(V_R\) Receiving-end line voltage V
\(P\) Load power W
\(\cos\phi\) Load power factor (lagging) -
\(r\) Resistance per phase per km Ω/m
\(l\) Inductance per phase per km H/m
\(c\) Capacitance per phase per km F/m
\(\ell\) Line length m
\(f\) Frequency 1/s
\(|Z_c|\) Characteristic (surge) impedance Ω
\(|\gamma\ell|\) Electrical length γℓ -
\(|A|\) Magnitude of A = cosh γℓ -
\(V_S\) Sending-end line voltage V
\(I_S\) Sending-end current A
\(\cos\phi_S\) Sending-end power factor -
\(\eta\) Efficiency -
\(\text{Reg}\) Voltage regulation -
\(SIL\) Surge impedance loading W

Method and standards

Exact hyperbolic solution of the telegrapher's equations.

Where it is used

  • EHV transmission planning and voltage control studies.
  • Checking reactive compensation on long lines.

Common mistakes

  • Using the nominal-π model for very long lines.
  • Mixing line-to-line and phase voltages.

Assumptions and limits

  • Balanced three-phase, steady state, uniform line, shunt conductance neglected.

References

  • Distributed-parameter (hyperbolic) long-line equations

Questions and answers

When must a line be treated as long?

Above about 250 km at 50–60 Hz; the nominal-π model then misjudges the voltage and charging current, and the exact model is needed.

What is |γℓ|?

The electrical length in radians: about 0.06 rad per 100 km at 50 Hz; a quarter-wavelength line (1,500 km at 50 Hz) would be π/2.

What do the defaults represent?

An illustrative 400 kV, 350 km line carrying 300 MW at 0.9 power factor, with 0.03 Ω/km, 1.0 mH/km and 11.5 nF/km.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Stevenson, Elements of Power System Analysis, 4th ed. (McGraw-Hill, 1982), ch. 6

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.