Worked example
Example: Illustrative: 400 kV, 350 km, 300 MW at 0.9. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Receiving-end line voltage | 400.00 kV |
| Load power | 300.00 MW |
| Load power factor (lagging) | 90.000 % |
| Resistance per phase per km | 0.030000 Ω/km |
| Inductance per phase per km | 1.0000 mH/km |
| Capacitance per phase per km | 11.500 nF/km |
| Line length | 350.00 km |
| Frequency | 50.000 Hz |
Applying the formula below gives:
| Result | Value |
|---|---|
| Characteristic (surge) impedance | 295.55 Ω |
| Electrical length |γℓ| | 0.37373 |
| Magnitude of A = cosh γℓ | 0.93130 |
| Sending-end line voltage | 426.54 kV |
| Sending-end current | 414.50 A |
| Sending-end power factor | 0.99927 |
| Efficiency | 98.039 % |
| Voltage regulation | 14.500 % |
| Surge impedance loading | 541.36 MW |
Open this example in the calculator and change any input.
Formula
\(\gamma = \sqrt{zy}, \quad Z_c = \sqrt{z/y}, \quad A = D = \cosh\gamma\ell, \quad B = Z_c\sinh\gamma\ell, \quad C = \frac{\sinh\gamma\ell}{Z_c}\)
\(V_S = AV_R + BI_R, \quad I_S = CV_R + AI_R\)
Variables
| Symbol | Meaning | SI unit | ||
|---|---|---|---|---|
| \(V_R\) | Receiving-end line voltage | V | ||
| \(P\) | Load power | W | ||
| \(\cos\phi\) | Load power factor (lagging) | - | ||
| \(r\) | Resistance per phase per km | Ω/m | ||
| \(l\) | Inductance per phase per km | H/m | ||
| \(c\) | Capacitance per phase per km | F/m | ||
| \(\ell\) | Line length | m | ||
| \(f\) | Frequency | 1/s | ||
| \(|Z_c|\) | Characteristic (surge) impedance | Ω | ||
| \(|\gamma\ell|\) | Electrical length | γℓ | - | |
| \(|A|\) | Magnitude of A = cosh γℓ | - | ||
| \(V_S\) | Sending-end line voltage | V | ||
| \(I_S\) | Sending-end current | A | ||
| \(\cos\phi_S\) | Sending-end power factor | - | ||
| \(\eta\) | Efficiency | - | ||
| \(\text{Reg}\) | Voltage regulation | - | ||
| \(SIL\) | Surge impedance loading | W |
Method and standards
Exact hyperbolic solution of the telegrapher's equations.
Where it is used
- EHV transmission planning and voltage control studies.
- Checking reactive compensation on long lines.
Common mistakes
- Using the nominal-π model for very long lines.
- Mixing line-to-line and phase voltages.
Assumptions and limits
- Balanced three-phase, steady state, uniform line, shunt conductance neglected.
References
- Distributed-parameter (hyperbolic) long-line equations
Questions and answers
When must a line be treated as long?
Above about 250 km at 50–60 Hz; the nominal-π model then misjudges the voltage and charging current, and the exact model is needed.
What is |γℓ|?
The electrical length in radians: about 0.06 rad per 100 km at 50 Hz; a quarter-wavelength line (1,500 km at 50 Hz) would be π/2.
What do the defaults represent?
An illustrative 400 kV, 350 km line carrying 300 MW at 0.9 power factor, with 0.03 Ω/km, 1.0 mH/km and 11.5 nF/km.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Stevenson, Elements of Power System Analysis, 4th ed. (McGraw-Hill, 1982), ch. 6