Worked example
Example: Illustrative 150 MWh at 0.88 to 0.99. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Monthly energy (kWh) | 150,000 - |
| Present average power factor | 88.000 % |
| Improved power factor | 99.000 % |
| Tariff per kVAh | 8.5000 - |
| Average load | 300.00 kW |
Applying the formula below gives:
| Result | Value |
|---|---|
| kVAh at present power factor | 170,455 |
| kVAh at improved power factor | 151,515 |
| Present bill | 1,448,864 |
| Monthly saving | 160,985 |
| Capacitor size at the average load | 119.18 kvar |
Open this example in the calculator and change any input.
Formula
\(E_S = \frac{E}{pf}, \quad \Delta B = cE\left(\frac{1}{pf_1} - \frac{1}{pf_2}\right), \quad Q_c = P(\tan\varphi_1 - \tan\varphi_2)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(E\) | Monthly energy (kWh) | - |
| \(pf_1\) | Present average power factor | - |
| \(pf_2\) | Improved power factor | - |
| \(c\) | Tariff per kVAh | - |
| \(P\) | Average load | W |
| \(E_{S,1}\) | kVAh at present power factor | - |
| \(E_{S,2}\) | kVAh at improved power factor | - |
| \(B_1\) | Present bill | - |
| \(\Delta B\) | Monthly saving | - |
| \(Q_c\) | Capacitor size at the average load | var |
Method and standards
kVAh billing.
Where it is used
- Industrial tariff savings studies.
- Capacitor bank business cases.
Common mistakes
- Comparing kWh tariffs with kVAh tariffs directly.
- Sizing capacitors for peak instead of average load.
Assumptions and limits
- Average power factor over the month.
References
- Apparent-energy billing
Questions and answers
How much does 0.88 to 0.99 save under kVAh billing?
About 11 % of the energy bill, since kVAh falls in proportion to 1/pf.
Why avoid leading power factor?
Over-compensation raises kVAh again, and many tariffs treat leading as lagging; it can also raise voltage at light load.
What do the defaults represent?
An illustrative factory using 150,000 kWh a month at an average 300 kW, power factor 0.88 raised to 0.99, tariff 8.5 per kVAh.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Pansini, Electrical Distribution Engineering, 3rd ed. (Fairmont, 2007)