Worked example
Example: Illustrative 3.3 MVA at 3 MW, pf 0.9. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Inverter apparent power rating | 3.3000 MVA |
| Real power output | 3.0000 MW |
| Minimum power factor allowed | 90.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Reactive limit from the rating √(S² − P²) | 1.3748 Mvar |
| Reactive limit from the power factor P tan φ | 1.4530 Mvar |
| Reactive power available | 1.3748 Mvar |
| Real power at which the rating limit binds | 2.9700 MW |
Open this example in the calculator and change any input.
Formula
\(Q_{max} = \min\left(\sqrt{S^2 - P^2},\;P\tan(\arccos pf_{min})\right)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(S\) | Inverter apparent power rating | VA |
| \(P\) | Real power output | W |
| \(pf_{min}\) | Minimum power factor allowed | - |
| \(Q_S\) | Reactive limit from the rating √(S² − P²) | var |
| \(Q_{pf}\) | Reactive limit from the power factor P tan φ | var |
| \(Q_{max}\) | Reactive power available | var |
| \(P_{Q,full}\) | Real power at which the rating limit binds | W |
Method and standards
PQ capability.
Where it is used
- Grid code compliance for solar and wind plants.
- Inverter sizing.
Common mistakes
- Assuming full reactive power at rated real power.
- Ignoring voltage-dependent limits.
Assumptions and limits
- Nominal voltage; ideal capability circle.
References
- Inverter PQ capability
Questions and answers
Why oversize an inverter's kVA?
At full real power a 1.0 × P inverter has no headroom for reactive power; a 1.1 × P rating gives about 46 % of P in reactive power.
What limits reactive power at low output?
Usually the power-factor setting or grid-code limits rather than the current rating.
What do the defaults represent?
An illustrative 3.3 MVA inverter exporting 3 MW with a 0.9 minimum power factor.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Gilbert Masters, Renewable and Efficient Electric Power Systems (Wiley, 2004), ch. 9