Inverter Reactive Power Capability at an Output

Reactive power an inverter can supply or absorb at a real power output from its kVA rating and minimum power factor.

Thermal power plant

Inputs

Examples: Illustrative 3.3 MVA at 3 MW, pf 0.9Part load 1 MWUnoversized 100 kVA at 100 kW

Accepted: 0.0001 to 1,000 MVA
Accepted: 0 to 1,000 MW
Accepted: 10 to 100 %

Results

Capability circle Q ≤ √(S² − P²) intersected with the power-factor limit Q ≤ P tan(acos pf). Many grid codes require reactive capability at full output, so inverters are oversized in apparent power (e.g. 1.1 × P).

Reactive limit from the rating √(S² − P²)1.3748Mvar
Reactive limit from the power factor P tan φ1.4530Mvar
Reactive power available1.3748Mvar
Real power at which the rating limit binds2.9700MW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 3.3 MVA at 3 MW, pf 0.9. The inputs, in the units selected above:

InputValue
Inverter apparent power rating3.3000 MVA
Real power output3.0000 MW
Minimum power factor allowed90.000 %

Applying the formula below gives:

ResultValue
Reactive limit from the rating √(S² − P²)1.3748 Mvar
Reactive limit from the power factor P tan φ1.4530 Mvar
Reactive power available1.3748 Mvar
Real power at which the rating limit binds2.9700 MW

Open this example in the calculator and change any input.

Formula

\(Q_{max} = \min\left(\sqrt{S^2 - P^2},\;P\tan(\arccos pf_{min})\right)\)

Variables

Symbol Meaning SI unit
\(S\) Inverter apparent power rating VA
\(P\) Real power output W
\(pf_{min}\) Minimum power factor allowed -
\(Q_S\) Reactive limit from the rating √(S² − P²) var
\(Q_{pf}\) Reactive limit from the power factor P tan φ var
\(Q_{max}\) Reactive power available var
\(P_{Q,full}\) Real power at which the rating limit binds W

Method and standards

PQ capability.

Where it is used

  • Grid code compliance for solar and wind plants.
  • Inverter sizing.

Common mistakes

  • Assuming full reactive power at rated real power.
  • Ignoring voltage-dependent limits.

Assumptions and limits

  • Nominal voltage; ideal capability circle.

References

  • Inverter PQ capability

Questions and answers

Why oversize an inverter's kVA?

At full real power a 1.0 × P inverter has no headroom for reactive power; a 1.1 × P rating gives about 46 % of P in reactive power.

What limits reactive power at low output?

Usually the power-factor setting or grid-code limits rather than the current rating.

What do the defaults represent?

An illustrative 3.3 MVA inverter exporting 3 MW with a 0.9 minimum power factor.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Gilbert Masters, Renewable and Efficient Electric Power Systems (Wiley, 2004), ch. 9

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.