Generator Size for Starting a Large Motor

Generator kVA needed so a large motor starting on it keeps the transient voltage dip within a limit, from motor rating, starter and subtransient reactance.

Thermal power plantProcess steam and utilities

Inputs

Examples: Illustrative 75 kW DOL, 15 % dipStar-delta 110 kW, 20 % dipSoft start 200 kW, 15 % dip

Accepted: 1 to 20,000 kW
Accepted: 50 to 100 %
Accepted: 30 to 100 %
Accepted: 1 to 10
Accepted: 10 to 100 %
Accepted: 0.05 to 0.4
Accepted: 5 to 40 %
Accepted: 30 to 100 %

Results

Dip ≈ X''_dS_s/(S_g + X''_dS_s), so S_g = X''_dS_s(1 − ΔV)/ΔV. This ignores the voltage regulator and engine response; makers' motor-starting curves give the final check. Reduced-voltage starters or VFDs cut the generator size sharply.

Motor running kVA241.98kVA
Motor starting kVA786.45kVA
Generator kVA for the dip limit534.79kVA
Generator kVA for running302.48kVA
Generator kVA needed534.79kVA

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 75 kW DOL, 15 % dip. The inputs, in the units selected above:

InputValue
Motor rated output75.000 kW
Motor efficiency93.000 %
Motor running power factor86.000 %
Locked-rotor current / rated current6.5000 -
Starter kVA factor (DOL 1, star-delta 0.33, soft start about 0.5)100.00 %
Generator subtransient reactance (per unit)0.15000 -
Allowed voltage dip15.000 %
Planned running load (share of rating)80.000 %

Applying the formula below gives:

ResultValue
Motor running kVA93.773 kVA
Motor starting kVA609.53 kVA
Generator kVA for the dip limit518.10 kVA
Generator kVA for running117.22 kVA
Generator kVA needed518.10 kVA

Open this example in the calculator and change any input.

Formula

\(S_s = k_{LR}k_s\frac{P_m}{\eta\,pf}, \quad S_g = \max\left(X''_dS_s\frac{1 - \Delta V}{\Delta V},\;\frac{S_r}{\lambda}\right)\)

Variables

Symbol Meaning SI unit
\(P_m\) Motor rated output W
\(\eta\) Motor efficiency -
\(pf\) Motor running power factor -
\(k_{LR}\) Locked-rotor current / rated current -
\(k_s\) Starter kVA factor (DOL 1, star-delta 0.33, soft start about 0.5) -
\(X''_d\) Generator subtransient reactance (per unit) -
\(\Delta V_{max}\) Allowed voltage dip -
\(\lambda\) Planned running load (share of rating) -
\(S_r\) Motor running kVA VA
\(S_s\) Motor starting kVA VA
\(S_{g,start}\) Generator kVA for the dip limit VA
\(S_{g,run}\) Generator kVA for running VA
\(S_g\) Generator kVA needed VA

Method and standards

Motor-start dip.

Where it is used

  • Diesel generator selection.
  • Standby and island power systems.

Common mistakes

  • Sizing only for running kW.
  • Ignoring the starter type.

Assumptions and limits

  • Single motor start; regulator response ignored.

References

  • Voltage dip on a generator from motor starting kVA

Questions and answers

Why does one motor drive generator size?

A direct-on-line start draws about six times running kVA at low power factor; the generator's reactance turns that into a deep voltage dip.

How much does a soft starter help?

It roughly halves starting kVA; a VFD reduces it to near running current, often allowing a much smaller set.

What do the defaults represent?

An illustrative 75 kW motor started direct on line (6.5 × rated current) on a generator with X''_d = 0.15, allowing a 15 % dip.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Grainger and Stevenson, Power System Analysis (McGraw-Hill, 1994)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.